Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
0.0 A / real32
Defines the nominal motor current. This setting must
match the value on the rating plate of the motor. If
multiple motors are connected to the drive, enter the
total current of the motors.
Note: Correct motor operation requires that the
magnetizing current of the motor does not exceed 90%
of the nominal current of the drive.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
current
99.6
1 = 1 A / 10 = 1 A
Nominal current of the motor. The allowable range is
1/6…2 ×
I
N
(nominal current) of the drive and 0…2 ×
I
N
with scalar control mode.
For ESP application, the recommended range is
1/3...2 ×
I
N
(nominal current) of the drive.
0.0 ... 6400.0 A
0.0 V / real32
Defines the nominal motor voltage supplied to the
motor. This setting must match the value on the rating
plate of the motor.
Note: With permanent magnet motors the nominal
voltage is the motor nominal total voltage scaled to
low voltage side.
Note: The stress on the motor insulation is always
dependent on the drive supply voltage. This also applies
to the case where the motor voltage rating is lower
than that of the drive and the supply.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
voltage
99.7
10 = 1 V / 10 = 1 V
Nominal voltage of the motor. The allowable range is
1/6…2 ×
U
N
(nominal voltage) of the drive.
U
N
equals
the upper bound of the supply voltage range selected
by parameter
0.0 ... 800.0 V
50.00 Hz / real32
Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
frequency
99.8
10 = 1 Hz / 100 = 1 Hz
Nominal frequency of the motor.
0.00 ... 1000.00 Hz
0 rpm / real32
Defines the nominal motor speed. The setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the
drive is running.
Note: (Asynchronous generator) Nominal speed needs
to be adjusted as running the generator as a motor.
Motor nominal
speed
99.9
1 = 1 rpm / 1 = 1 rpm
Nominal speed of the motor.
0...30000 rpm
622 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...