Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Values of references received from various sources.
Input references
3
All parameters in this group are read-only unless
otherwise noted.
0.00 / real32
Local reference given from the control panel or PC tool.
Panel reference
3.1
10 = 1 / 100 = 1
Local control panel or PC tool reference.
-100000.00 ...
100000.00
- / real32
Remote reference given from the control panel or PC
tool.
Panel reference 2
3.2
10 = 1 / 100 = 1
Remote control panel or PC tool reference.
-30000.00 ...
30000.00
0.00 / real32
Reference 1 received through fieldbus adapter A.
See also chapter
Fieldbus control through a fieldbus
FB A reference 1
3.5
10 = 1 / 100 = 1
Reference 1 from fieldbus adapter A.
-100000.00 ...
100000.00
0.00 / real32
Reference 2 received through fieldbus adapter A.
FB A reference 2
3.6
10 = 1 / 100 = 1
Reference 2 from fieldbus adapter A.
-100000.00 ...
100000.00
0.00 / real32
Reference 1 received through fieldbus adapter B.
FB B reference 1
3.7
10 = 1 / 100 = 1
Reference 1 from fieldbus adapter B.
-100000.00 ...
100000.00
0.00 / real32
Reference 2 received through fieldbus adapter B.
FB B reference 2
3.8
10 = 1 / 100 = 1
Reference 2 from fieldbus adapter B.
-100000.00 ...
100000.00
- / real32
Scaled reference 1 received through the embedded
fieldbus interface. The scaling is defined by
.
EFB reference 1
3.9
10 = 1 / 100 = 1
Reference 1 received through the embedded fieldbus
interface.
-30000.00 ...
30000.00
- / real32
Scaled reference 2 received through the embedded
fieldbus interface. The scaling is defined by
.
EFB reference 2
3.10
10 = 1 / 100 = 1
Reference 2 received through the embedded fieldbus
interface.
-30000.00 ...
30000.00
- / real32
Reference 1 received from the external (DDCS)
controller.
DDCS controller ref
1
3.11
The value has been scaled according to parameter
60.60 DDCS controller ref1 type
See also section
External controller interface (page 81)
.
10 = 1 / 100 = 1
Scaled reference 1 received from external controller.
-30000.00 ...
30000.00
- / real32
Reference 2 received from the external (DDCS)
controller.
DDCS controller ref
2
3.12
The value has been scaled according to parameter
Parameters 179
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...