Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
0 ms / uint16
Defines a minimum response delay in addition to any
fixed delay imposed by the protocol.
Changes to this parameter take effect after the control
unit is rebooted or the new settings validated by
parameter
.
Transmit delay
58.17
1 = 1 ms / 1 = 1 ms
Minimum response delay.
0...65535 ms
0 / uint32
Displays the raw (unmodified) control word sent by the
Modbus controller to the drive. For debugging
purposes.
This parameter is read-only.
EFB control word
58.18
1 = 1
Control word sent by Modbus controller to the drive.
00000000…FFFFFFFFh
0 / uint32
Displays the raw (unmodified) status word sent by the
drive to the Modbus controller. For debugging
purposes.
This parameter is read-only.
EFB status word
58.19
1 = 1
Status word sent by the drive to the Modbus controller.
00000000…FFFFFFFFh
ABB Drives / uint16
Defines the control profile used by the protocol.
Control profile
58.25
0
ABB Drives profile (with a 16-bit control word) with
registers in the classic format for backward
compatibility.
ABB Drives
2
Transparent profile (16-bit or 32-bit control word) with
registers in the classic format.
Transparent
Auto / uint16
Selects the type and scaling of reference 1 received
through the embedded fieldbus interface.
The scaled reference is displayed by
.
EFB ref1 type
58.26
0
Type and scaling are chosen automatically according
to which reference chain (see settings
,
) the incoming reference is connected to. If
the reference is not connected to any chain, no scaling
is applied (as with setting
Auto
1
No scaling is applied.
Transparent
2
Generic reference with a scaling of 100 = 1 (ie. integer
and two decimals).
General
3
The scaling is defined by parameter
Torque
4
The scaling is defined by parameter
Speed
5
The scaling is defined by parameter
.
Frequency
Torque / uint16
Selects the type and scaling of reference 2 received
through the embedded fieldbus interface.
The scaled reference is displayed by
For the selections, see parameter
EFB ref2 type
58.27
Auto / uint16
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through the
embedded fieldbus interface.
EFB act1 type
58.28
484 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...