Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1
The external event generates a warning.
Warning
3
If the drive is modulating, the external event generates
a fault.
Otherwise, the event generates a warning.
Warning/Fault
Inactive (true) /
uint32
Defines the source of external event 4. See also
parameter
For the selections, see parameter
.
External event 4
source
31.7
Fault / uint16
Selects the type of external event 4.
External event 4
type
31.8
0
The external event generates a fault.
Fault
1
The external event generates a warning.
Warning
3
If the drive is modulating, the external event generates
a fault.
Otherwise, the event generates a warning.
Warning/Fault
Inactive (true) /
uint32
Defines the source of external event 5. See also
parameter
For the selections, see parameter
.
External event 5
source
31.9
Fault / uint16
Selects the type of external event 5.
External event 5 type
31.10
0
The external event generates a fault.
Fault
1
The external event generates a warning.
Warning
3
If the drive is modulating, the external event generates
a fault.
Otherwise, the event generates a warning.
Warning/Fault
DI3 / uint32
Selects the source of an external fault reset signal. This
signal will be observed even if it is not the active source
in the current control location (EXT1/EXT2/Local).
(A reset from the active source will be observed
regardless of this parameter.)
0 → 1 = Reset
Fault reset selection
31.11
0
0
Not selected
1
1
Selected
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
Parameters 367
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...