background image

 

 

Features 

 

Control panel operator convenience features: 

 

Wide viewing angle 2 x 20 (40 character) alphanumeric 
LCD and dedicated LEDs provide convenient panel 
status information 

 

Operation is programmable using a multi-function 
keypad and the panel LCD or via service computer (PC) 

 

RS-232 service port provides upload/download PC 
access for panel configuration and event history logs 

 

Software updates are via PC download 

 

Convenient library of standard custom label terms 

 

Standard on-board DACT provides: Contact ID, 3/1, 4/2, 
BFSK, and SIA formats 

 

WALKTEST silent or audible system test 

 

Voltage and current for both the battery charger and the 
battery can be displayed at the front panel LCD 

Five Standard Initiating Device Circuits (IDCs): 

 

Five Class B IDCs with optional expansion to ten, all 
with individual zone disable 

 

Monitor 2-wire or 4-wire initiating devices including 
TrueAlarm smoke detectors 

 

Optional Class A Adapter Module 

Two Standard Notification Appliance Circuits (NACs): 

 

Class A or Class B outputs with solid state overcurrent 
protection per NAC, each rated for 2 A 

 

Selectable for Simplex

®

 SmartSync two-wire 

horn/strobe control or synchronized strobe control 

Standard Power Supply: 

 

Provides 3 A maximum @ nominal 24 DC 

 

Automatic input power selection operates with 120 VAC 
or 240 VAC, 50 or 60 Hz 

 

On-board temperature compensated battery charger for 
up to 12.7 Ah batteries in cabinet (UL and ULC) and up 
to 25 Ah batteries in separate cabinet (UL only) 

Additional standard features: 

 

Programmable Active Status Reminder 

 

Two auxiliary relays 

 

IDCs, NACs, and Relay outputs are power limited (AC 
input, battery circuits, and City Circuit Module outputs 
are non-power limited) 

 

Available with beige or red cabinet 

 

UL listed to Standard 864 

Available option modules: 

 

Door mounted 24 LED annunciator (standard on ULC 
models) 

 

3 A Expansion Power Supply with two on-board 2 A 
NACs that operate the same as standard NACs 

ALARM

ACK

SUPV
ACK

TROUBLE

ACK

ALARM

SILENCE

SYSTEM

RESET

FIRE

ALARM

SYSTEM

SUPERVISORY

SYSTEM

TROUBLE

ALARM

SILENCED

AC

POWER

 

4006-9102 (Beige) Standard Control Panel 

 

ALARM

ACK

SUPV
ACK

TROUBLE

ACK

ALARM

SILENCE

SYSTEM

RESET

FIRE

ALARM

SYSTEM

SUPERVISORY

SYSTEM

TROUBLE

ALARM

SILENCED

AC

POWER

F i r e     A l a r m     A n n u n c i a t o r

CAUTION

DISCONNECT

BATTERY  AND

A. C.  POWER

BEFORE

SERVICING

 

4006-9122 (Beige) Control Panel with 24 LED Annunciator 

 

Available option modules (Continued)

 

Expansion IDC module with five Class B IDCs 

 

Class A IDC Adapter Module, City Interface Module, 
and Auxiliary Relay Module 

 

Remote LCD and LED/Switch Annunciators 

 

Description 

 

For areas requiring from five to ten initiating zones, the 
Simplex 4006 Series fire alarm control panels provide 
flexible initiating circuit monitoring, extensive 
programmable control capability, and LCD annunciated 
circuit-specific 20 character custom labels.  

 

*

    See page 2 for additional ULC and MEA information. This product has been approved by 

the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California 

Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or 

conditions concerning material presented in this document. It is subject to re-examination, 

revision, and possible cancellation. Additional listings may be applicable, contact your local 

Simplex product supplier for the latest status. Listings and approvals under Simplex Time 

Recorder Co. are the property of Tyco Fire Protection Products. 

 

 

LifeAlarm Fire Alarm Control Panels 

UL, ULC, CSFM Listed; FM Approved;

 

 4006 Series Fire Alarm Control Panels

 

MEA (NYC) Acceptance*

 

Providing up to Ten IDCs and Four NACs

 

 

 

S4006-0001-8  8/2012

 

 

Содержание 4006 Series

Страница 1: ... cabinet UL listed to Standard 864 Available option modules Door mounted 24 LED annunciator standard on ULC models 3 A Expansion Power Supply with two on board 2 A NACs that operate the same as standard NACs ALARM ACK SUPV ACK TROUBLE ACK ALARM SILENCE SYSTEM RESET FIRE ALARM SYSTEM SUPERVISORY SYSTEM TROUBLE ALARM SILENCED AC POWER 4006 9102 Beige Standard Control Panel ALARM ACK SUPV ACK TROUBLE...

Страница 2: ...tional auxiliary power output of 500 mA Output operation is the same as on the standard power supply Expansion IDC Module Provides 5 additional Class B IDCs with operation the same as the standard IDCs Expansion Relay Module Provides 10 programmable relays jumper selectable as N O or N C Contacts are rated 2 A 30 VDC Typical application is to track status of each IDC See page 7 for relay program o...

Страница 3: ...arm list SUPV ACK acknowledges system supervisory conditions logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Supervisory list TROUBLE ACK acknowledges system troubles logs the acknowledge silences the operator panel and all annunciator tone alerts and steps through the active Trouble list FIVE NAVIGATION KEYS MENU selects the on screen ...

Страница 4: ...t 500 mA maximum 24 VDC Standard Auxiliary Relay Outputs Relay 1 Programmable operation Contacts rated 2 A 30 VDC 0 35 power factor jumper selectable as N O or N C Relay 2 Trouble operation Wiring Connections for Above Circuits and AC Input Terminals rated for 18 AWG to 12 AWG 0 82 mm2 to 3 31 mm2 Option Module Ratings Class A IDC Adapter Module Five circuits per module rated same as circuits Ten ...

Страница 5: ...n Alarm 4006 9121 4006 9122 Control panel with 24 LED Annunciator 148 mA 210 mA 60 mA per IDC in Alarm 4006 9801 Expansion Power Supply 50 mA 60 mA 4006 9802 Expansion IDC Module 50 mA 50 mA 60 mA per IDC in Alarm 4006 9803 Expansion Relay Module 0 mA 10 mA per energized relay 0 mA 10 mA per energized relay 4006 9804 Five Circuit IDC Class A Adapter 0 mA normal 10 mA per IDC in trouble 0 mA normal...

Страница 6: ...TROUBLE VSMOKE Verified fire alarm the abnormal current limited state causes the alarm verification cycle to start a short is an immediate alarm Normal Current Limited Short Open NORMAL VERIFY FIRE TROUBLE STYLEC Style C fire monitor Normal Current Limited Short Open NORMAL FIRE TROUBLE TROUBLE LATSUPV Latching supervisory monitor supervisory latches until system is reset Normal Current Limited Sh...

Страница 7: ...West Front Center rear 5th Flr_1 Flr_2 Flr_3 Flr_4 Flr_5 RM_ Basement Floor Garage Hallway HVAC_Room Kitchen Lobby Office Patient upper lower main first 2nd 3rd 4th Boiler_RM Classroom Closet_ Corridor Elect_RM Elevator Entrance Restroom Room Stairway Storeroom Wing Zone History logs Three separate logs Alarm 100 entries Supervisory 100 entries and Trouble 300 entries logs can be queried separatel...

Страница 8: ...Main board Knockouts are located on top and sides Expansion Power Supply extends under IDC Expansion Module space Display Assembly Box depth 4 3 4 121 mm 16 406 mm Door thickness 5 8 16 mm NOTE For semi flush mounting cabinet must extend 1 1 2 38 mm minimum from wall surface Tyco Fire Protection Products Westminster MA 01441 0001 USA S4006 0001 8 8 2012 www simplexgrinnell com 2012 Tyco Fire Prote...

Отзывы: