384
YASKAWA
TOEPYAIGA5002A GA500 Programming
Makes the best motor acceleration rate for start up. If you set this parameter to 1, it will make acceleration smoother,
but it can also increase the acceleration time to be longer than the set time. If the drive detects
oC [Overcurrent]
faults
immediately after acceleration starts, set this parameter.
0 : No
1 : Yes
Note:
Set
L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]
to enable this function.
◆
L4: Speed Detection
L4 parameters
set the output of signals to the MFDO terminals, for example frequency agree and speed detection.
■
L4-01: Speed Agree Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
L4-01
(0499)
Speed Agree Detection
Level
Sets the level to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the level to detect speed agree or motor speed when
H2-01 to H2-03 = 2, 3, 4, 5 [MFDO Function Selection =
Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2]
.
■
L4-02: Speed Agree Detection Width
No.
(Hex.)
Name
Description
Default
(Range)
L4-02
(049A)
Speed Agree Detection
Width
Sets the width to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the width to detect speed agree or motor speed when
H2-01 to H2-03 = 2, 3, 4, 5 [MFDO Function Selection =
Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2]
.
■
L4-03: Speed Agree Detection Level(+/-)
No.
(Hex.)
Name
Description
Default
(Range)
L4-03
(049B)
Speed Agree Detection
Level(+/-)
Sets the level to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the level to detect speed agree or motor speed when
H2-01 to H2-03 = 13, 14, 15, 16 [MFDO Function Selection
= Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4]
.
■
L4-04: Speed Agree Detection Width(+/-)
No.
(Hex.)
Name
Description
Default
(Range)
L4-04
(049C)
Speed Agree Detection
Width(+/-)
Sets the width to detect speed agree or motor speed.
Determined by A1-02
(Determined by A1-02)
Sets the width to detect speed agree or motor speed when
H2-01 to H2-03 = 13, 14, 15, 16 [MFDO Function
Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4]
.
■
L4-05: Fref Loss Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
L4-05
(049D)
Fref Loss Detection
Selection
Sets the operation when the drive detects a loss of frequency reference.
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...