390
YASKAWA
TOEPYAIGA5002A GA500 Programming
Figure 2.123 Overtorque Detection Time Chart
Note:
The drive applies a hysteresis of approximately 10% of the drive rated output current or the motor rated torque to the overtorque/undertorque
detection function.
Undertorque Detection Time Chart
When you use Overtorque/Undertorque Detection 1, the drive detects undertorque if the motor current or motor
torque is less than or equal to the detection level set in
L6-02
for the time set in
L6-03
. Parameter
L6-01
sets the
operation after detection.
When you use Overtorque/Undertorque Detection 2, set the operation in
L6-04, L6-05, and L6-06
.
Set the terminal that outputs an alarm in
H2-01 to H2-03
.
Figure 2.124 Undertorque Detection Time Chart
Note:
The drive applies a hysteresis of approximately 10% of the drive rated output current or the motor rated torque to the overtorque/undertorque
detection function.
■
Mechanical Weakening Detection
The Mechanical Weakening Detection function detects the mechanical weakening of a machine that can cause
overtorque or undertorque because of motor speed and total drive operation time.
The drive activates the function if the drive total operation time is longer than the time set in
L6-11 [Mech Fatigue
Hold Off Time]
. You can use
U4-01 [Cumulative Ope Time]
to monitor the total operation time.
Parameter Settings
If overtorque or undertorque occur during the speed range set in
L6-08 [Mechanical Fatigue Detect Select]
and
L6-09
[Mech Fatigue Detect Speed Level]
for the length of time set in
L6-10 [Mech Fatigue Detect Delay Time]
, the drive
will detect Mechanical Weakening. The drive uses
L6-01 to L6-03 [Torque Detection 1 Setting Parameter]
to detect
oL5 [Mechanical Weakening Detection 1]
or
UL5 [Mechanical Weakening Detection 2]
. Parameter
L6-08
sets the
operation after detection.
Set the terminal that outputs the fault in
H2-01 to H2-03 [MFDO Function Selection]
.
Table 2.65 Mechanical Weakening Detection Settings Parameters
Configuration Parameter
Mechanical Deterioration Detection
MFDO Function Select
•
Terminal MA-MC
•
Terminal P1-C1
•
Terminal P2-C2
H2-01, H2-02, and H2-03 = 22
Operation Selection after Detection
L6-08
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...