YASKAWA
TOEPYAIGA5002A GA500 Programming
217
Figure 2.43 Speed Control Block Diagram for AOLV/PM and EZOLV
Note:
The detected speed is the speed estimation value when configured such that
A1-02 = 6 or 8 [Control Method Selection = AOLV/PM or
EZOLV]
.
■
Before You Adjust ASR Parameters
•
Do Auto-Tuning and set up all motor data correctly.
•
Always make adjustments with the load connected to the motor.
•
Use analog output signals to monitor
U1-16 [SFS Output Frequency]
and
U1-05 [Motor Speed]
when you adjust
the ASR.
■
ASR Adjustment Procedure for AOLV/PM and EZOLV
Do this procedure to adjust ASR parameters:
1. Run the motor at zero speed or low speed and increase
C5-01 [ASR Proportional Gain 1]
until immediately
before vibration starts to occur.
2. Run the motor at zero speed or low speed and decrease
C5-02 [ASR Integral Time 1]
until immediately before
vibration starts to occur.
3. Check for oscillation when you run the motor at maximum speed.
4. If oscillation occurs, increase
C5-02
and decrease
C5-01
.
When there is no oscillation, the adjustment procedure is complete.
5. Set the low-speed gain. Run the motor at zero speed or low speed and increase
C5-03 [ASR Proportional Gain 2]
until immediately before vibration starts to occur.
Figure 2.44 Low-speed/High-speed Gain Settings
6. Set the low-speed integral time. Run the motor at zero speed or low speed and decrease
C5-04 [ASR Integral Time
2]
until immediately before vibration starts to occur.
7. Set
C5-07 [ASR Gain Switchover Frequency]
.
8. Check for oscillation when you run the motor at speeds more than the setting in
C5-07
.
Note:
•
If overshooting occurs when acceleration ends, decrease the value set in
C5-01
and increase the value set in
C5-02
.
•
If undershoot occurs at stop, decrease
C5-03
and increase
C5-04
.
■
Use MFDI Switch for Proportional Gain
You can use the input terminals set for ASR Gain (C5-03) Select
[H1-xx = 77]
to switch the proportional gains set
with
C5-01
and
C5-03
. When the configured input terminal is deactivated, the proportional gain set for
C5-01
is
selected. When the terminal is activated, the proportional gain set for
C5-03
is selected. The proportional gain
changes linearly over the time set in
C5-02 [ASR Integral Time 1].
The signals from this MFDI are more important
than
C5-07 [ASR Gain Switchover Frequency]
.
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...