YASKAWA
TOEPYAIGA5002A GA500 Programming
375
Note:
When
A1-02 = 5 [Control Method Selection = OLV/PM]
, the setting range is
0
and
1
.
Stall prevention during acceleration prevents the stalling and stopping of motors when the drive detects
oC
[Overcurrent]
,
oL2 [Drive Overloaded]
, or
oL1 [Motor Overload]
when you apply a large load during acceleration or
when you set sudden acceleration times related to load inertia.
0 : Disable
The Stall Prevention function does not operate during acceleration, and acceleration occurs for the set acceleration
time. If the acceleration time is too short, the motor does not fully accelerate during the set time, which causes the
drive to detect
oL1
or
oL2
and the motor to stop.
1 : Enabled
Enables the Stall Prevention During Acceleration function. Operation is different for different control methods.
•
V/f Control, Open Loop Vector Control, or EZ Open Loop Vector Control
When the output current is more than the value set in
L3-02 [Stall Prevent Level during Accel]
, the drive stops
acceleration. The drive stops deceleration when the output current is less than
L3-02
- 15%. The Stall Prevention
function level automatically decreases for constant output ranges.
Figure 2.114 Stall Prevention During Acceleration when Using Induction Motors
•
Open Loop Vector Control for PM
When the output current is more than
L3-02
, the drive stops acceleration. When the time set in
L3-27 [Stall
Prevention Detection Time]
is expired and the output current =
L3-02
, the drive will start deceleration as specified
by the value set in
L3-22 [PM Stall Prevention Decel Time]
. The drive starts acceleration again when the output
current is less than
L3-02
- 15%. When the time set in
L3-27
is expired, the drive starts acceleration again.
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...