2.2 A: Initialization Parameters
152
YASKAWA
TOEPYAIGA5002A GA500 Programming
Table 2.18 Adjustment of Drive Control (Open Loop Vector Control Method)
Adjustment description
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Torque, increase speed response
•
Prevent hunting and oscillation
at middle-range speeds (10 Hz
to 40 Hz)
n2-01 [Automatic Freq Regulator
Gain]
•
If torque and speed response are
slow, decrease the setting value.
•
If there is hunting or oscillation,
increase the setting value.
1.00
0.50 - 2.00
•
Torque, increase speed response
•
Prevent hunting and oscillation
C4-02 [Torque Compensation
Delay Time]
•
If torque and speed response are
slow, decrease the setting value.
•
If there is hunting or oscillation,
increase the setting value.
20 ms
20 ms to 100 ms
•
Increase speed response
•
Increase speed stability
C3-02 [Slip Compensation Delay
Time]
•
When speed response is slow,
decrease the setting value.
•
If speed is not stable, increase
the setting value.
200 ms
100 ms to 500 ms
•
Improve speed accuracy
C3-01 [Slip Compensation Gain]
•
If speed is too slow, increase the
setting value.
•
If speed is too fast, decrease the
setting value.
1.0
0.5 - 1.5
•
Increasing motor excitation
sound
•
Prevent hunting and oscillation
at low-range speeds (10 Hz to
or lower)
C6-02 [Carrier Frequency
Selection]
•
If there is a loud motor
excitation sound, increase the
setting value.
•
If there is hunting or oscillation
at low speeds, decrease the
setting value.
1 - F
•
Increase torque and speed
response at low speeds
•
Prevent shock during start up
E1-08 [Mid Point A Voltage]
•
If the torque and speed response
are slow, increase the setting
value.
•
If there is a large shock during
start up, decrease the setting
value.
11.0 V
12.0 V to 13.0 V
E1-10 [Minimum Output Voltage]
2.0 V
2.0 V to 3.0 V
*1
If the value for
C4-02 [Torque Compensation Delay Time]
is high, the current can increase during start up. Adjust and check the current
during start up.
*2
The default setting changes when the settings for
C6-01 [Normal / Heavy Duty Selection]
and
o2-04 [Drive Model (KVA) Selection]
change.
*3
This is the setting for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
Elevator Start/Stop and Accel/Decel Time Shock Reduction
S-Curve Characteristics, Accel & Decel Time
Adjustment Parameter
Name
C1-01, C1-03, C1-05, C1-07
Acceleration Time 1 to 4
C1-02, C1-04, C1-06, C1-08
Deceleration Time 1 to 4
C2-01
S-Curve Time @ Start of Accel
C2-02
S-Curve Time @ End of Accel
C2-03
S-Curve Time @ Start of Decel
C2-04
S-Curve Time @ End of Decel
Figure 2.4 S-curve Characteristics, Accel & Decel Time
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...