2.8 H: Terminal Function Selection
304
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
47: Node Setup (CANopen)
Setting Value
Function
Description
47
Node Setup (CANopen)
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from the host
controller.
■
60: DC Injection Braking Command
Setting Value
Function
Description
60
DC Injection Braking
Command
Sets the command to use DC Injection Braking to stop the motor.
If you input the Run command or JOG command, it will cancel DC Injection Braking.
shows the time chart of the DC Injection Braking function.
Figure 2.69 DC Injection Braking Time Chart
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available with a PM motor.
•
Refer to
b2: DC Injection Braking and Short Circuit Braking on page 168
for more information.
■
61: Speed Search from Fmax
Setting Value
Function
Description
61
Speed Search from Fmax
Sets the function to start speed search using an external reference although
b3-01 = 0 [Speed Search Selection at Start = Disabled]
.
When the terminal is turned ON for
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
, the drive
starts speed search from the maximum output frequency.
Note:
•
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
•
Refer to
“
b3: Speed Search
”
for more information.
■
62: Speed Search from Fref
Setting Value
Function
Description
62
Speed Search from Fref
Sets the function to use an external reference to start speed search although
b3-01 = 0 [Speed Search Selection at Start = Disabled]
.
When the terminal is turned ON for
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
, the drive
starts speed search from the frequency reference.
Note:
•
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
•
Refer to
“
b3: Speed Search
”
for more information.
■
63: Field Weakening
Setting Value
Function
Description
63
Field Weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in
d6-01[Field
Weakening Level] and d6-02 [Field Weakening Frequency Limit]
when the input terminal is activated.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...