o3-06: Auto Parameter Backup Selection
No.
(Hex.)
Name
Description
Default
(Range)
o3-06
(0BDE)
Auto Parameter Backup
Selection
Sets the function that automatically backs up parameters. This parameter is only available when
using an LCD keypad.
1
(0, 1)
When you connect the drive and keypad, parameters set to the drive are automatically backed up to the keypad as
specified by the setting of parameters
o3-06
and
o3-07
.
0 : Disabled
1 : Enabled
Note:
When you replace the LCD keypad then energize the drive, the keypad shows the restore operation screen automatically to restore the drive
configuration with the parameters backed up to the LCD keypad. If you connect an LCD keypad that does not have parameter backup data,
the keypad will not show the restore operation screen.
■
o3-07: Auto Parameter Backup Interval
No.
(Hex.)
Name
Description
Default
(Range)
o3-07
(0BDF)
Auto Parameter Backup
Interval
Sets the interval at which the automatic parameter backup function saves parameters from the drive
to the keypad.
1
(0 - 3)
The drive saves parameter settings to the keypad at these times:
1. After you energize the drive and the auto backup period passes.
2. When you use ROM enter or the keypad to change parameters, the drive saves those changes in the drive, waits
for the auto backup period to pass, then saves those parameters in the keypad.
Note:
The drive can write data to the keypad a maximum of 100,000 times. If you write data to the keypad more than 100,000 times, you must
replace the keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
◆
o4: Maintenance Mon Settings
o4 parameters
set the expected service life to help you know when to replace parts. The drive will show an alarm to
tell you when the replacement part interval is near.
■
o4-01: Elapsed Operating Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
When you select
o4-01
on the keypad, it will show the current value of
U4-01
in units of 10 hours (h). When you
change the setting of
o4-01
through the monitor, the
U4-01
count starts again as specified by the setting of
o4-01
.
Note:
Set this parameter in 10-hour (h) units. When
o4-01 = 30
,
U4-01 [Cumulative Ope Time] = 300 h
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...