YASKAWA
TOEPYAIGA5002A GA500 Programming
57
Setting Value
Function
Description
Ref.
4
Frequency Detection 1
The terminal deactivates when the output frequency is higher than the value of
L4-01 [Speed Agree Detection Level] +
L4-02 [Speed Agree Detection Width]
. After the terminal turns off, the terminal continues to remain off until the output
frequency reaches the level set with
L4-01
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
ON : The output frequency is less than the value of
L4-01
or does not exceed the value of
L4-01
+
L4-02
.
OFF : The output frequency is higher than the value of
L4-01
+
L4-02
.
5
Frequency Detection 2
The terminal activates when the output frequency is higher than the value of
L4-01 [Speed Agree Detection Level]
.
After the terminal activates, the terminal stays activated until the output frequency is at the value of
L4-01
-
L4-02
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
ON : The output frequency is higher than the value of
L4-01
.
OFF : The output frequency is less than the value of
“
L4-01
-
L4-02
,
”
or it does not exceed the value of
L4-01
.
6
Drive ready
The terminal activates when the drive is ready and running.
7
DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with
L2-05
[Undervoltage Detection Lvl (Uv1)]
. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of
L2-05
.
OFF : The DC bus voltage is more than the setting value of
L2-05
.
8
During Baseblock (N.O.)
The terminal turns on during baseblock. When the drive is in baseblock, the drive output transistor stops switching and
does not make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
9
Frequency Reference
from Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : Parameter
b1-01 or b1-15 [Frequency Reference Selection 1 or 2]
is the frequency reference source.
A
Run Command Source
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : Parameter
b1-02
or
b1-16
[Run Command Selection 1 or 2] is the Run command source.
B
Torque Detection 1 (N.
O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque >
L6-02 [Torque Detection Level 1]
, or <
L6-02
for longer than the time set with
L6-03
[Torque Detection Time 1]
.
C
Frequency Reference
Loss
The terminal activates when the drive detects a loss of frequency reference.
D
Braking Resistor Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor
fault.
E
Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for
CPF00
and
CPF01 [Control Circuit Error]
faults.
F
Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via MEMOBUS/Modbus or the communication option. This signal does not function if signals from the PLC
are not configured.
10
Alarm
The terminal turns on when the drive detects a minor fault.
11
Fault Reset Command
Active
The terminal turns on when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
12
Timer Output
Use this setting when the drive uses the timer function as an output terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...