YASKAWA
TOEPYAIGA5002A GA500 Programming
31
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
d1-12
(028D)
RUN
Reference 12
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the default setting is
o1-03
= 1 [0.01% (100% = E1-04)]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-13
(028E)
RUN
Reference 13
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the default setting is
o1-03
= 1 [0.01% (100% = E1-04)]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-14
(028F)
RUN
Reference 14
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the default setting is
o1-03
= 1 [0.01% (100% = E1-04)]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-15
(0290)
RUN
Reference 15
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the default setting is
o1-03
= 1 [0.01% (100% = E1-04)]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-16
(0291)
RUN
Reference 16
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the default setting is
o1-03
= 1 [0.01% (100% = E1-04)]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from
o1-03 [Frequency Display Unit
Selection]
. Set
H1-xx = 6 [MFDI Function Select = Jog Reference Selection]
to use the
Jog frequency reference.
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the default setting is
o1-03
= 1 [0.01% (100% = E1-04)]
.
6.00 Hz
(0.00 - 590.00 Hz)
◆
d2: Reference Limits
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
d2-01
(0289)
Frequency Reference
Upper Limit
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum
output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Motor Max Revolutions]
100.0%
(0.0 - 110.0%)
d2-02
(028A)
Frequency Reference
Lower Limit
Sets minimum limit for all frequency references. The maximum output frequency is 100%.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum
output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Motor Max Revolutions]
0.0%
(0.0 - 110.0%)
d2-03
(0293)
Analog Frequency Ref
Lower Limit
Sets the lower limit for the master frequency reference (the first frequency of the multi-
step speed reference) as a percentage. The maximum output frequency is 100%.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum
output frequency.
•
A1-02 ≠ 8
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
0.0%
(0.0 - 110.0%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...