258
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
E5-01: PM Motor Code Selection
No.
(Hex.)
Name
Description
Default
(Range)
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
FFFF
(0000 - FFFF)
Note:
•
If the drive hunts or shows an alarm after you enter a motor code, use the keypad to enter the value shown on the nameplate to
E5-xx
.
•
When you use a PM motor other than a Yaskawa SMRD, SMRA, or SSR1 series, set
E5-01 = FFFF
.
gives information about the motor code setting digits.
Figure 2.59 PM Motor Code
■
E5-02: PM Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04, C6-01
(0.10 - 30.00 kW)
These Auto-Tuning methods will automatically set this parameter:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM Rotational Auto-Tuning
■
E5-03: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
Motor Rated Current (FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023
•
0.1 A: 2056 - 2082, 4031 - 4060
The drive automatically sets
E5-03
to the value input for
T2-06 [PM Motor Rated Current]
after you do these types of
Auto-Tuning:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM Stationary Tuning for Stator Resistance
•
PM Rotational Auto-Tuning
■
E5-04: PM Motor Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E5-04
(032C)
PM Motor Pole Count
Sets the number of PM motor poles.
4
(2 - 120)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...