Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
•
MFDI (terminals S1 to S7)
•
Pulse train output (terminal MP)
•
MFAI (terminal A2)
•
MFAO (terminal AM)
•
MEMOBUS/Modbus communications (terminals D+, D-, AC)
◆
Pulse Train Output
You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.
•
Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
R
L
(k
Ω
)
Output Voltage
V
MP
(V)
1.5 kΩ or more
5 V or more
4.0 kΩ or more
8 V or more
10 kΩ or more
10 V or more
Note:
Use the formula in
to calculate the necessary load resistance (kΩ) to increase output voltage V
MP
(V).
A - Load Impedance
Figure 5.6 Wiring to Use Pulse Train Output in Sourcing Mode
•
Use in sinking mode
The external power supply changes the voltage level of the pulse train output signal. Keep the voltage from an
external source between 10.8 Vdc to 16.5 Vdc. Adjust the load impedance to keep the current at 16 mA or lower.
External Power Supply (V)
Load Impedance (k
Ω
)
Sinking current (mA)
10.8 Vdc to 16.5 Vdc
1.0 kΩ or more
16 mA maximum
A - External power supply
B - Load Impedance
C - Sinking current
Figure 5.7 Wiring to Use Pulse Train Output in Sinking Mode
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...