2.2 A: Initialization Parameters
YASKAWA
TOEPYAIGA5002A GA500 Programming
147
User Parameter No.
Parameter No. Saved
Name
A2-08
d2-01
Frequency Reference Upper Limit
A2-09
d2-02
Frequency Reference Lower Limit
A2-10
E1-03
V/f Pattern Selection
A2-11
E1-04
Maximum Output Frequency
A2-12
E2-01
Motor Rated Current (FLA)
A2-13
H3-11
Terminal A2 Gain Setting
A2-14
H3-12
Terminal A2 Bias Setting
A2-15
L2-01
Power Loss Ride Through Select
A2-16
o4-12
kWh Monitor Initialization
5 : Air Compressor
The drive automatically sets the parameters in
for an air compressor application.
Table 2.12 Best Parameter Settings for Air Compressor Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
C1-01
Acceleration Time 1
5.0 s
C1-02
Deceleration Time 1
5.0 s
C6-01
Normal / Heavy Duty Selection
0: Heavy Duty Rating
E1-03
V/f Pattern Selection
F: Custom
L2-01
Power Loss Ride Through Select
1: Enabled for L2-02 Time
L3-04
Stall Prevention during Decel
1: General Purpose
The drive saves the parameters in
as User Parameters.
Table 2.13 Parameters Saved as User Parameters with the Air Compressor Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-01
Frequency Reference Selection 1
A2-02
b1-02
Run Command Selection 1
A2-03
b1-04
Reverse Operation Selection
A2-04
C1-01
Acceleration Time 1
A2-05
C1-02
Deceleration Time 1
A2-06
E1-03
V/f Pattern Selection
A2-07
E1-07
Mid Point A Frequency
A2-08
E1-08
Mid Point A Voltage
A2-09
E2-01
Motor Rated Current (FLA)
8 : Conveyor 2
The drive automatically sets the parameters in
for a conveyor 2 application.
Table 2.14 Best Parameter Settings for Conveyor 2 Application
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Normal / Heavy Duty Selection
0: Heavy Duty Rating
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...