Set this parameter to 0.0 to disable the function. The drive uses the acceleration time in
C1-01, C1-03, C1-05, and C1-
07
to accelerate again after KEB operation completes.
■
L2-08: Frequency Gain at KEB Start
No.
(Hex.)
Name
Description
Default
(Range)
L2-08
(048C)
Expert
Frequency Gain at KEB
Start
Sets the quantity of output frequency reduction used when KEB operation starts as a percentage of
the motor rated slip before starting KEB operation.
100%
(0 - 300%)
Decreases the output frequency in steps to quickly set the motor to a regenerative condition. Use this formula to
calculate the value:
Output frequency reduction = Motor rated slip before KEB operation × (
L2-08
/100) × 2
■
L2-09: KEB Minimum Frequency Level
No.
(Hex.)
Name
Description
Default
(Range)
L2-09
(048D)
Expert
KEB Minimum Frequency
Level
Sets the quantity of output frequency reduction used as a percentage of
E2-02 [Motor Rated Slip]
when KEB operation starts.
20%
(0 - 100%)
These conditions set the quantity of decrease:
•
Motor rated slip × (
L2-09
/100)
•
The larger value between the value calculated with
L2-08
and the value calculated with
L2-09
■
L2-10: Minimum KEB Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-10
(048E)
Expert
Minimum KEB Time
Sets the minimum length of time to operate the KEB after the drive detects a momentary power loss.
50 ms
(0 - 25500 ms)
When you return power while KEB is operating, the drive continues KEB operation until the time set in
L2-10
is
expired. When the DC bus voltage is less than the level of
L2-05 [Undervoltage Detection Lvl (Uv1)]
in one of these
conditions, KEB operation continues until the time set in
L2-10
is expired:
•
L2-01 = 3 [Power Loss Ride Through Select = Kinetic Energy Backup: L2-02]
•
L2-01 = 4 [Kinetic Energy Backup: CPU Power]
•
L2-01 = 5 [Kinetic Energy Backup: DecelStop]
•
KEB Ride-Thru 1/2 [H1-xx = 65, 66, 7A, or 7B]
is input into the drive.
When you input KEB Ride-Thru, KEB operation continues after the time set in
L2-10
is expired. When you cancel
KEB Ride-Thru, the motor accelerates again. When you do not input KEB Ride-Thru during the time set in
L2-10
, the
drive accelerates to the frequency reference that the drive had before power loss in the applicable acceleration time.
When
L2-01 = 3, 4, or 5
, and the DC bus voltage is a minimum of the value of
L2-11 [KEB DC Bus Voltage
Setpoint]
, the drive accelerates again after the time set in
L2-10
is expired. When the DC bus voltage is less than the
L2-11
value, KEB operation continues after the time set in
L2-10
is expired.
Note:
•
When
L2-01 = 0, 1, or 2 [Disabled, Enabled for L2-02 Time, or Enabled while CPU Power Active]
, increase the value of
L2-10
. Set
L2-10
to cancel KEB operation if the KEB Ride-Thru is not input.
•
Setting
L2-10
to 0 ms disables the function of
L2-10
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...