2.8 H: Terminal Function Selection
308
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
7B: KEB Ride-Thru 2 Activate (N.O.)
Setting Value
Function
Description
7B
KEB Ride-Thru 2 Activate
(N.O.)
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The
L2-29
[KEB Method Selection]
setting will not have an effect.
Note:
•
If you set
KEB Ride-Thru 1 [H1-xx = 65, 66]
and
KEB Ride-Thru 2 [H1-xx = 7A, 7B]
at the same time, the drive will detect
oPE03 [Multi-
Function Input Setting Err]
.
•
Refer to
KEB Ride-Thru Function on page 364
for more information.
■
7C: Short Circuit Braking (N.O.)
Setting Value
Function
Description
7C
Short Circuit Braking (N.O.)
Sets operation of Short Circuit Braking (N.O.).
The drive will short circuit the three phases of a PM motor to cause braking torque in the spinning motor.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
•
Refer to
b2: DC Injection Braking and Short Circuit Braking on page 168
for more information.
ON : Short Circuit Braking is enabled.
OFF : Normal operation
■
7D: Short Circuit Braking (N.C.)
Setting Value
Function
Description
7D
Short Circuit Braking (N.C.)
Sets operation of Short Circuit Braking (N.C.).
The drive will short circuit the three phases of a PM motor to cause braking torque in the spinning motor.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
•
Refer to
b2: DC Injection Braking and Short Circuit Braking on page 168
for more information.
ON : Normal operation
OFF : Short Circuit Braking is enabled.
■
7E: Reverse Rotation Identifier
Setting Value
Function
Description
7E
Reverse Rotation Identifier
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
ON : Reverse run
The drive knows that the motor is rotating in the reverse direction.
OFF : Forward run
The drive knows that the motor is rotating in the forward direction.
■
90 to 96: DWEZ Digital Inputs 1 to 7
Setting Value
Function
Description
90 - 96
DWEZ Digital Inputs 1 to 7
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...