2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
329
■
3E: PID Feedback Low
Setting Value
Function
Description
3E
PID Feedback Low
The terminal activates when the drive detects
FbL [PID Feedback Loss]
.
The drive detects
FbL [PID Feedback Loss]
when the PID feedback value <
b5-13 [PID Feedback Loss Detection
Lvl]
for longer than
b5-14 [PID Feedback Loss Detection Time]
.
Note:
Refer to
PID Feedback Loss Detection on page 184
for more information.
■
3F: PID Feedback High
Setting Value
Function
Description
3F
PID Feedback High
The terminal activates when the drive detects
FbH [Excessive PID Feedback]
.
The drive detects
FbH [Excessive PID Feedback]
when the PID feedback value >
b5-36 [PID High Feedback
Detection Lvl]
for longer than
b5-37 [PID High Feedback Detection Time]
.
Note:
Refer to
PID Feedback Loss Detection on page 184
for more information.
■
4A: During KEB Ride-Thru
Setting Value
Function
Description
4A
During KEB Ride-Thru
The activates during KEB Ride-Thru.
Note:
Refer to
KEB Ride-Thru Function on page 364
for more information.
■
4B: During Short Circuit Braking
Setting Value
Function
Description
4B
During Short Circuit Braking
The terminal activates during Short Circuit Braking.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
•
Refer to
b2: DC Injection Braking and Short Circuit Braking on page 168
for more information.
■
4C: During Fast Stop
Setting Value
Function
Description
4C
During Fast Stop
The terminal activates when the fast stop is in operation.
■
4D: oH Pre-Alarm Time Limit
Setting Value
Function
Description
4D
oH Pre-Alarm Time Limit
The terminal activates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and
oH [Heatsink
Overheat]
does not clear after the drive decreases the frequency for 10 cycles.
Note:
Refer to
“
L8-03: Overheat Pre-Alarm Ope Selection
”
for more information about drive derating operation.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...