2.8 H: Terminal Function Selection
346
YASKAWA
TOEPYAIGA5002A GA500 Programming
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
■
H5-03: Communication Parity Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-03
(0427)
Communication Parity
Selection
Sets the communications parity used for MEMOBUS/Modbus communications.
0
(0 - 2)
Note:
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload Now]
after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
■
H5-04: Communication Error Stop Method
No.
(Hex.)
Name
Description
Default
(Range)
H5-04
(0428)
Communication Error Stop
Method
Sets the motor Stopping Method when the drive detects
CE [MEMOBUS/Modbus Communication
Err]
issues.
3
(0 - 3)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = E]
activates.
3 : Alarm Only
The keypad shows
CE
and the drive continues operation. The output terminal set for
Alarm [H2-01 to H2-03 = 10]
activates.
■
H5-05: Comm Fault Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-05
(0429)
Comm Fault Detection
Selection
Sets the function that detects
CE [Modbus Communication Error]
issues during MEMOBUS/
Modbus communications.
1
(0, 1)
If the drive does not receive data from the master during the time set in
H5-09 [CE Detection Time]
, it will detect a
CE
error.
0 : Disabled
Does not detect
CE
. The drive continues operation.
1 : Enabled
Detects
CE
. If the drive detects
CE
, it will operate as specified by the setting of
H5-04 [Communication Error Stop
Method]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...