2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
343
■
30: DWEZ Analog Input 1
Setting Value
Function
Description
30
DWEZ Analog Input 1
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
■
31: DWEZ Analog Input 2
Setting Value
Function
Description
31
DWEZ Analog Input 2
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
◆
H4: Analog Outputs
H4 parameters
set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
■
Calibrate Meters Connected to MFAO Terminal AM
Use these parameters to calibrate meters connected to terminal AM:
•
H4-02 [Terminal AM Analog Output Gain]
•
H4-03 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch
S5
and parameter
H4-07 [Terminal AM Signal Level Select]
to set the voltage output and current
output.
No.
Name
Range
Default
H4-02
Terminal AM Analog Output Gain
-999.9 - +999.9%
100.0%
H4-03
Terminal AM Analog Output Bias
-999.9 - +999.9%
0.0%
H4-07
Terminal AM Signal Level Select
0: 0 +10 VDC
2: 4-20 mA
0
and
show the gain and bias.
Figure 2.94 Analog Output Gain/Bias Configuration Example 1
For example, when the parameter value set to analog output is 0, and a 3 V signal is to be output to terminal AM, set
H4-03 [AM Analog Output Bias] = 30%
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...