1.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA
TOEPYAIGA5002A GA500 Programming
125
No.
Name
Unit
Default
-
Drive Model
-
4023
4031
4038
4044
C6-01
Normal /
Heavy Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model
(KVA)
Selection
Hex.
9A
9C
9D
9E
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW
7.5
11
11
15
15
18.5
18.5
22
E2-03
(E4-03)
Motor No-
Load Current
A
4
5.6
5.6
7.6
7.6
7.8
7.8
9.2
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω
1.152
0.922
0.922
0.55
0.55
0.403
0.403
0.316
E2-06
(E4-06)
Motor
Leakage
Inductance
%
15.5
19.6
19.6
17.2
17.2
20.1
20.1
23.5
E2-10
(E4-10)
Motor Iron
Loss
W
263
385
385
440
440
508
508
586
E5-01
PM Motor
Code Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Power Loss
Ride Through
Time
s
1
1
2
2
2
2
2
2
L2-03
Minimum
Baseblock
Time
s
0.8
0.9
0.9
1
1
1
1
1
L2-04
Powerloss V/f
Recovery
Ramp Time
s
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
L2-05
Undervoltage
Detection Lvl
(Uv1)
-
380
380
380
380
380
380
380
380
L3-02
Stall Prevent
Level during
Accel
%
150
120
150
120
150
120
150
120
L3-06
Stall Prevent
Level during
Run
%
150
120
150
120
150
120
150
120
L3-24
Motor Accel
Time @ Rated
Torque
s
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
L8-02
Overheat
Alarm Level
°C
120
120
120
120
120
120
125
125
L8-09
Output Ground
Fault
Detection
-
0
0
1
1
1
1
1
1
n1-03
Hunting
Prevention
Time Constant
ms
10
10
10
10
10
10
10
10
n3-02
HSB Current
Limit Level
%
150
120
150
120
150
120
150
120
n5-02
Motor Inertia
Acceleration
Time
s
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
*1
Parameters within parentheses are for motor 2.
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...