Table 3.9 EZ Tuning Mode Selection
Mode
Parameter
Settings
Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
Motor Parameter Setting
T4-01 = 0
•
Applicable when driving an induction motor or a PM motor
•
Suitable for derating torque applications, for example fans and
pumps.
EZOLV
(8)
Line-to-Line Resistance
T4-01 = 1
•
After Auto-Tuning, the wiring distance between the drive and
motor changed by 50 m or more.
•
When the motor output and drive capacity are different.
EZOLV
(8)
■
Auto-Tuning Input Data in EZ Open Loop Vector Control Method
To do Auto-Tuning, input data for the items in
that have an "x". Before you start Auto-Tuning, prepare the
motor test report or record the information from the motor nameplate as a reference.
Table 3.10 Auto-Tuning Input Data in EZ Open Loop Vector Control Method
Input Data
Parameter
Unit
Auto-Tuning Mode
(T4-01 Setting)
Motor Parameter
Setting
(0)
Line-to-Line Resistance
(1)
Motor Type Selection
T4-02
-
x
-
Motor Max Revolutions
T4-03
min
-1
x
-
Motor Rated Revolutions
T4-04
min
-1
x
-
Motor Rated Frequency
T4-05
Hz
x
-
Motor Rated Voltage
T4-06
V
x
-
Motor Rated Current (FLA)
T4-07
A
x
x
PM Motor Rated Power (kW)
T4-08
kW
x
x
Number of Motor Poles
T4-09
-
x
-
◆
ASR and Inertia Tuning
To increase drive responsiveness and prevent hunting, use Auto-Tuning to automatically adjust the control-related
parameters.
These types of Auto-Tuning are available for the control system:
•
Deceleration Rate Tuning
•
KEB Tuning
Note:
If you do Control Tuning, you cannot set
H1-xx = 16 [Motor 2 Selection]
. Do not do Control Tuning for applications that switch between
motor 1 and motor 2.
Table 3.11 Control Loop Tuning Selection
Mode
Parameter
Settings
Application Conditions and Benefits
Applicable Control Methods (A1-02 Settings)
V/f
(0)
OLV
(2)
OLV/PM
(5)
AOLV/PM
(6)
EZOLV
(8)
Deceleration Rate
Tuning
T3-00 = 2
To automatically adjust the deceleration rate to prevent
an
ov [Overvoltage]
fault.
x
x
x
x
x
KEB Tuning
T3-00 = 3
•
To automatically adjust parameter settings to
prevent an
ov [Overvoltage]
fault with the KEB
Ride-Thru function.
•
When
L3-11 = 1 [Overvoltage Suppression Select =
Enabled]
.
x
x
x
x
x
■
Deceleration Rate Tuning
Deceleration Rate Tuning automatically sets the deceleration rate to prevent an
ov [Overvoltage]
fault during motor
deceleration. Set
C1-11 [Accel/Decel Time Switchover Freq]
first to automatically set parameters
C1-02
[Deceleration Time 1]
(high speed range) and
C1-08 [Deceleration Time 4]
(low speed range).
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...