240
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
d6-01: Field Weakening Level
No.
(Hex.)
Name
Description
Default
(Range)
d6-01
(02A0)
Field Weakening Level
Sets the drive output voltage as a percentage of
E1-05 [Maximum Output Voltage]
when
H1-xx = 63
[Field Weakening]
is activated.
80%
(0 - 100%)
■
d6-02: Field Weakening Frequency Limit
No.
(Hex.)
Name
Description
Default
(Range)
d6-02
(02A1)
Field Weakening Frequency
Limit
Sets the minimum output frequency to start field weakening.
0.0 Hz
(0.0 - 590.0 Hz)
Make sure that these two conditions are correct to enable the Field Weakening command:
•
The output frequency ≥
d6-02
.
•
There is a speed agreement status.
■
d6-03: Field Forcing Selection
No.
(Hex.)
Name
Description
Default
(Range)
d6-03
(02A2)
Field Forcing Selection
Sets the field forcing function.
0
(0, 1)
0 : Disabled
1 : Enabled
■
d6-06: Field Forcing Limit
No.
(Hex.)
Name
Description
Default
(Range)
d6-06
(02A5)
Field Forcing Limit
Sets the limit value for field forcing to increase the motor excitation current reference as a percentage
of
E2-03 [Motor No-Load Current]
. Usually it is not necessary to change this setting.
400%
(100 - 400%)
Note:
You cannot use Field Forcing during DC Injection Braking.
◆
d7: Offset Frequency
The drive will use 3 digital signal inputs, to add or subtract the set frequency (Offset frequency) to/from the frequency
reference and correct the speed. The drive uses the terminal set in
H1-xx = 44 to 46 [MFDI Function Select = Add
Offset Frequency 1 to 3]
to set the Offset frequency. When you close more than one input at the same time, the drive
adds the selected offset values together.
shows the Offset frequency function:
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...