YASKAWA
TOEPYAIGA5002A GA500 Programming
55
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for
the monitor selected in
H2-20 [Comparator 1 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
H2-24
(1544)
Comparator 1 On-Delay
Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
H2-25
(1545)
Comparator 1 Off-Delay
Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the
x-xx
part of the
Ux-xx [Monitor]
. For
example, set
H2-26 = 103
to monitor
U1-03 [Output Current]
.
103
(000 - 999)
H2-27
(1547)
Comparator 2 Lower
Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 300.0%)
H2-28
(1548)
Comparator 2 Upper
Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 300.0%)
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for
the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
H2-32
(159A)
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output
of the monitor selected with
H2-20 [Comparator 1 Monitor Selection]
.
0.0s
(0.0 - 10.0 s)
H2-33
(159B)
Comparator1 Protection
Selection
Sets drive operation when it detects
CP1 [Comparator1 Limit Fault]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
4
(0 - 4)
H2-34
(159C)
Comparator 2 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output
of the monitor selected with
H2-26 [Comparator 2 Monitor Selection]
.
0.0s
(0.0 - 10.0 s)
H2-35
(159D)
Comparator2 Protection
Selection
Sets drive operation when it detects
CP2 [Comparator2 Limit Fault]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
4
(0 - 4)
H2-36
(159E)
Comparator 1 Ineffective
Time
Sets the length of time that
CP1 [Comparator1 Limit Fault]
is disabled.
0.0 s
(0.0 - 1000.0 s)
H2-37
(159F)
Comparator 2 Ineffective
Time
Sets the length of time that
CP2 [Comparator2 Limit Fault]
is disabled.
0.0 s
(0.0 - 1000.0 s)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
H2-60
(1B46)
Expert
Term MA,MB,MC
Secondary Function
Sets the second function for terminal MA/MB-MC. Outputs the logical calculation results
of the terminals set to functions by
H2-01 [Term MA,MB,MC Function Selection]
.
F
(0 - FF)
H2-61
(1B47)
Expert
Term MA,MB,MC
Logical Operation
Sets the logical operation for the functions set in
H2-01 [Term MA,MB,MC Function
Selection]
and
H2-60 [Term MA,MB,MC Secondary Function]
.
0
(0 - 8)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...