2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
297
■
12: Forward Jog
Setting Value
Function
Description
12
Forward Jog
Sets the command to operate the motor in the forward direction at the Jog Frequency set in
d1-17 [Jog Reference]
.
Note:
•
It is not necessary to input the Run command.
•
The Forward JOG command has priority over all other frequency references.
•
When the Forward JOG and Reverse JOG commands are activated at the same time for 500 ms or longer, the drive will ramp to stop.
Figure 2.65 JOG Operation Pattern
■
13: Reverse Jog
Setting Value
Function
Description
13
Reverse Jog
Sets the command to operate the motor in reverse at the Jog Frequency set in
d1-17 [Jog Reference]
.
Note:
•
It is not necessary to input the Run command.
•
The Reverse JOG command has priority over all other frequency references.
•
When the Forward JOG and Reverse JOG commands are activated at the same time for 500 ms or longer, the drive will ramp to stop.
■
14: Fault Reset
Setting Value
Function
Description
14
Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
If the drive detects a fault, the drive will activate the fault relay output, turn off the output, and the motor will coast to
stop.
If the drive detects a fault for which you can set the stopping method, apply the appropriate Stopping Method. Then
push
(RESET) on the keypad to turn the Run command OFF, or activate the fault reset terminal to reset the fault.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a fault.
■
15: Fast Stop (N.O.)
Setting Value
Function
Description
15
Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is activated while
the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
•
Fully stop the motor
•
Cancel the Run command
•
Cancel the fast stop command
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...