2.8 H: Terminal Function Selection
312
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
H2-03: Term P2-C2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
2
(0 - 1FF)
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in through mode.
■
H2-06: Watt Hour Output Unit Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when
H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output]
.
0
(0 - 4)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. The drive triggers a 200 ms pulse
each time the KWh data is at the value set in
H2-06
. This parameter sets the kWh unit for each pulse output.
Figure 2.72 Example MFDO when Configured for Watt Hours
Note:
•
When the power value is a negative value (regenerative state), the drive does not count Watt hours.
•
When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive to
lose control power, the Watt hour count will reset.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
■
H2-07: Modbus Register 1 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to
Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62]
and uses the bit
in
H2-08 [Modbus Register 1 Bit Select]
.
■
H2-08: Modbus Register 1 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to
Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62]
and uses the address
in
H2-07 [Modbus Register 1 Address Select]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...