TOEPYAIGA5002A GA500 Programming
Table 5.2 Multi-function Input Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Digital Inputs
S1
MFDI selection 1
(ON: Forward run, OFF: Stop)
•
Photocoupler
•
24 V, 6 mA
Note:
To set the MFDI power supply (Sinking/Sourcing Mode or internal/external power supply), install
or remove a jumper between terminals SC-SP or SC-SN depending on the application.
•
Sinking Mode, Internal power supply: Install the jumper to close the circuit between terminals
SC-SP.
NOTICE:
Damage to Equipment. Do not close the circuit between
terminals SC-SN. If you close the circuits between terminals SC-SP
and terminals SC-SN at the same time, it will cause damage to the
drive.
•
Sourcing Mode, Internal power supply: Install the jumper to close the circuit between terminals
SC-SN.
NOTICE:
Damage to Equipment. Do not close the circuit between
terminals SC-SP. If you close the circuits between terminals SC-SP
and terminals SC-SN at the same time, it will cause damage to the
drive.
•
External power supply: Remove the jumper from the MFDI terminals. It is not necessary to close
the circuit between terminals SC-SP and terminals SC-SN.
S2
MFDI selection 2
(ON: Reverse run OFF: Stop)
S3
MFDI selection 3
(External fault (N.O.))
S4
MFDI selection 4
(Fault reset)
S5
MFDI selection 5
(Multi-step speed reference 1)
S6
MFDI selection 6
(Multi-step speed reference 2)
S7
MFDI selection 7
(Jog command)
SN
MFDI power supply 0 V
MFDI power supply, 24 V (maximum 150 mA)
NOTICE:
Damage to Equipment. Do not close the circuit between
terminals SP-SN. If you close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause damage to the drive.
SC
MFDI selection common
SP
MFDI power 24 Vdc
Safe Disable
Input
H1
Safe Disable input 1
Remove the jumper between terminals H1-HC and H2-HC to use the Safe Disable input.
•
24 V, 6 mA
•
ON: Normal operation
•
OFF: Coasting motor
•
Internal impedance 4.7 kΩ
•
OFF Minimum OFF time of 3 ms.
H2
Safe Disable input 2
HC
Safe Disable function common
Safe Disable function common
NOTICE:
Do not close the circuit between terminals HC and SN. A
closed circuit between these terminals will cause damage to the drive.
Master
Frequency
Reference
RP
Master frequency reference pulse train input
(Master frequency reference)
•
Response frequency: 0 to 32 kHz
•
H level duty: 30% to 70%
•
H level voltage: 3.5 V to 13.2 V
•
L level voltage: 0.0 V to 0.8 V
•
Input impedance: 3 kΩ
+V
Power supply for frequency setting
10.5 V (allowable current 20 mA maximum)
A1
MFAI1
(Master frequency reference)
Voltage input
Use
H3-01 [Terminal A1 Signal Level Select]
to select the signal level.
•
0 V to 10 V/ 100% (input impedance: minimum 15 kΩ)
•
-10 V to +10 V/-100% to +100% (input impedance: minimum 15 kΩ)
A2
MFAI2
(Combined to terminal A1)
Voltage input or current input
Use DIP switch S1 and
H3-09 [Terminal A2 Signal Level Select]
to select the input.
•
0 V to 10 V/ 100% (input impedance: minimum 15 kΩ)
•
-10 V to +10 V/-100% to +100% (input impedance: minimum 15 kΩ)
•
4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
AC
Frequency reference common
0 V
■
Output Terminals
Refer to
and
for a list of Output terminals and functions.
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...