3.7 Fine Tuning during Test Runs (Adjust the Control Function)
482
YASKAWA
TOEPYAIGA5002A GA500 Programming
◆
Open Loop Vector Control Method
In Open Loop Vector Control, keep
C4-01 [Torque Compensation Gain]
at its default setting (1.00).
If you cannot get speed precision during regeneration in Open Loop Vector Control, set
C3-04 = 1 [Slip
Compensation at Regen = Enabled Above 6 Hz]
.
Table 3.15 Parameters for Fine Tuning the Drive (
A1-02 = 2 [OLV]
)
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Unsatisfactory motor torque
and speed response
•
Hunting or oscillation at mid-
range speeds (10 Hz to 40 Hz)
n2-01 [Automatic Freq Regulator
Gain]
•
To increase the speed of torque
or speed response, decrease the
setting value in 0.05-unit
increments.
•
If hunting or oscillation occur,
decrease the setting value in
0.05-unit increments.
1.00
0.50 to 2.00
n2-02 [Automatic Freq Regulator
Time 1]
•
To increase the speed of torque
or speed response, decrease the
setting value in 10 ms
increments and examine the
response.
•
If hunting or oscillation occur
or if the load inertia is too
much, increase the setting value
in 50 ms increments and
examine the response.
Note:
Make sure that this parameter
setting is:
n2-02 ≤ n2-03
[Automatic Freq Regulator
Time 2]
.
When you adjust
n2-02
, you
must also increase the
C4-02
[Torque Compensation Delay
Time]
value by the same ratio.
50 ms
50 ms to 2000 ms
ov [Overvoltage]
occurs when the
drive stops accelerating, starts to
decelerate, or when there are large
changes in the load.
n2-03 [Automatic Freq Regulator
Time 2]
•
If
ov
occurs, increase the setting
value in 50 ms increments and
examine the response.
•
If the response is not sufficient,
decrease the setting value in 10
ms increments and examine the
response.
Note:
Make sure that this parameter
setting is:
n2-02 [Automatic
Freq Regulator Time 1] ≤ n2-
03
. When you adjust
n2-03
,
you must also increase the
C4-
06 [Motor 2 Torque Comp
Delay Time]
value by the same
ratio.
750 ms
750 ms to 2000 ms
C4-06 [Motor 2 Torque Comp
Delay Time]
•
If
ov
occurs, increase the setting
value in 10 ms increments and
examine the response.
•
If the response is not sufficient,
decrease the setting value in 2
ms increments and examine the
response.
Note:
Make sure that this parameter
setting is:
C4-02 [Torque
Compensation Delay Time] ≤
C4-06
.
When you adjust
C4-06
, you
must also increase the
n2-03
[Automatic Freq Regulator
Time 2]
value by the same
ratio.
150 ms
150 ms to 750 ms
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...