YASKAWA
TOEPYAIGA5002A GA500 Programming
183
Table 2.26 Input Methods for the PID Setpoint
Input Methods for the PID Setpoint
Setting Value
MFAI terminal A1
Set
H3-02 = C [Terminal A1 Function Selection = PID Setpoint]
.
MFAI terminal A2
Set
H3-10 [Terminal A2 Function Selection] = C
.
MEMOBUS/Modbus register 0006H
Sets MEMOBUS/Modbus register 000FH (Control Selection Setting) bit 1 to 1 (PID
setpoint input). Enters the PID setpoint to MEMOBUS/Modbus register 0006H (PID
Target, 0.01% units, signed).
Pulse train input terminal RP
Set
H6-01 = 2 [Terminal RP Pulse Train Function = PID Setpoint Value]
.
b5-19 [PID Setpoint Value]
Set
b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled]
. Enters the PID setpoint to
b5-19
.
Note:
If you set two inputs for the PID setpoint, it will trigger operation error
oPE07 [Analog Input Selection Error]
.
■
Entering the PID Feedback Value
You can use two methods to input the PID feedback value to the drive. One method uses a single feedback signal for
usual PID control. The other method uses two signals. The difference between those signals sets the deviation.
•
Use a single feedback signal.
Use
to select how the feedback signal is input to the drive for PID control.
Table 2.27 PID Feedback Input Method
PID Feedback Input Method
Setting Value
MFAI terminal A1
Set
H3-02 = B [PID Feedback]
.
MFAI terminal A2
Set
H3-10 = B
.
Pulse train input terminal RP
Set
H6-01 = 1 [PID Feedback Value]
.
•
Use two signals, and use the difference between those signals as the feedback signal.
The drive uses two feedback signals, and the difference between those signals becomes the deviation.
Use
to select how the second feedback value is input to the drive. The drive calculates the deviation of
the second feedback value. Set
H3-02 or H3-10 = 16 [Terminal A1 or A2 Function Selection = Differential PID
Feedback]
to enable the second feedback signal used to calculated the deviation.
Table 2.28 PID Differential Feedback Input Method
PID Differential Feedback Input Method
Setting Value
MFAI terminal A1
Set
H3-02 = 16 [Differential PID Feedback]
.
MFAI terminal A2
Set
H3-10 = 16
.
Note:
If you set
H3-02 and H3-10 = 16
, it will trigger
oPE07 [Analog Input Selection Error]
.
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...