2.3
b: Application
b parameters
set these functions:
•
Frequency reference source/Run command source
•
Stopping method settings
•
DC Injection Braking
•
Speed Search
•
Timer Function
•
PID control
•
Dwell function
•
Energy-Saving Control
◆
b1: Operation Mode Selection
b1 parameters
set the operation mode for the drive.
■
b1-01: Frequency Reference Selection 1
No.
(Hex.)
Name
Description
Default
(Setting Range)
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
1
(0 - 4)
Note:
•
Push
on the keypad to set the input mode to LOCAL and use the keypad to enter the frequency reference.
•
If the frequency reference is 0 Hz or less than the value set in
E1-09 [Minimum Output Frequency]
and the drive receives the Run
command, the RUN LED on the keypad will flash. Examine the setting for the frequency reference input and enter a value ≥ E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1 and A2 to input an analog frequency reference with a voltage or current input signal.
•
Voltage Input
Refer to
to use a voltage signal input to one of the MFAI terminals.
Table 2.19 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection
Gain
Bias
A1
0 - 10 V
H3-01 = 0
H3-02 = 0
[Frequency Reference]
H3-03
H3-04
-
-10 - +10 V
H3-01 = 4
A2
0 - 10 V
H3-09 = 0
H3-10 = 0
[Frequency Reference]
H3-11
H3-12
Set DIP switch S1 to
“
V
”
for
voltage input.
-10 - +10 V
H3-09 = 4
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...