2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
287
2.8
H: Terminal Function Selection
H parameters
set functions for external input and output terminals.
◆
H1: Digital Inputs
H1 Parameters
set the MFDI terminal functions.
■
H1-01 to H1-07 Terminal S1 to S7 Function Selection
The drive has 7 MFDI terminals. Refer to
for drive default settings and functions.
Table 2.48 MFDI Default Settings and Functions
No.
Name
Default
Function
H1-01
Terminal S1 Function Selection
40 (F)
Forward RUN (2-Wire)
H1-02
Terminal S2 Function Selection
41 (F)
Reverse RUN (2-Wire)
H1-03
Terminal S3 Function Selection
24
External Fault (NO-Always-Coast)
H1-04
Terminal S4 Function Selection
14
Fault Reset
H1-05
Terminal S5 Function Selection
3 (0)
Multi-Step Speed Reference 1
H1-06
Terminal S6 Function Selection
4 (3)
Multi-Step Speed Reference 2
H1-07
Terminal S7 Function Selection
6 (4)
Jog Reference Selection
*1
The value in parentheses identifies the default setting when you set
A1-03 = 3330 [Initialize Parameters = 3-Wire Initialization]
.
Refer to the
and use
H1-xx [MFDI Function Select]
to set the function.
Table 2.49 MFDI Setting Values
Setting Value
Function
Reference
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Overheat Alarm (oH2)
C
Analog Terminal Enable Selection
E
ASR Integral Reset
F
Through Mode
10
Up Command
11
Down Command
Forward Jog
Reverse Jog
14
Fault Reset
Fast Stop (N.O.)
16
Motor 2 Selection
Setting Value
Function
Reference
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Programming Lockout
1E
Reference Sample Hold
20 to 2F
External fault
30
PID Integrator Reset
31
PID Integrator Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter Disable
35
PID Input (Error) Invert
3E
PID Setpoint Selection 1
3F
PID Setpoint Selection 2
40
Forward RUN (2-Wire)
41
Reverse RUN (2-Wire)
42
Run Command (2-Wire Sequence 2)
43
FWD/REV (2-Wire Sequence 2)
44
Add Offset Frequency 1 (d7-03)
45
Add Offset Frequency 2 (d7-03)
46
Add Offset Frequency 3 (d7-03)
47
Node Setup (CANopen)
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...