2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
303
ON : Reverse Run
OFF : Run Stop
Note:
•
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm EF [FWD/REV Run Command
Input Error] and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)]
.
■
42: Run Command (2-Wire Sequence 2)
Setting Value
Function
Description
42
Run Command (2-Wire
Sequence 2)
Sets the Run command for 2-wire sequence 2. Set this function and
H1-xx = 43 [FWD/REV Command (2-Wire Seq 2)]
at the same
time.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as
H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)]
.
■
43: FWD/REV (2-Wire Sequence 2)
Setting Value
Function
Description
43
FWD/REV (2-Wire
Sequence 2)
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and
H1-xx = 42 [Run Command (2-Wire Sequence 2)]
together.
ON : Reverse
OFF : Forward
Note:
•
You must input the Run command to rotate the motor.
•
This function will not operate at the same time as
H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)]
.
■
44: Add Offset Frequency 1 (d7-01)
Setting Value
Function
Description
44
Add Offset Frequency 1 (d7-
01)
Sets the function to add the offset frequency set in
d7-01 [Offset Frequency 1]
to the frequency reference when the terminal
activates.
Note:
Refer to
d7: Offset Frequency on page 240
for more information.
■
45: Add Offset Frequency 2 (d7-02)
Setting Value
Function
Description
45
Add Offset Frequency 2 (d7-
02)
Sets the function to add the offset frequency set in
d7-02 [Offset Frequency 2]
to the frequency reference when the terminal
activates.
Note:
Refer to
d7: Offset Frequency on page 240
for more information.
■
46: Add Offset Frequency 3 (d7-03)
Setting Value
Function
Description
46
Add Offset Frequency 3 (d7-
03)
Sets the function to add the offset frequency set in
d7-03 [Offset Frequency 3]
to the frequency reference when the terminal
activates.
Note:
Refer to
d7: Offset Frequency on page 240
for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...