2.8 H: Terminal Function Selection
302
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
35: PID Input (Error) Invert
Setting Value
Function
Description
35
PID Input (Error) Invert
Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
Note:
Refer to
“
PID control block diagram
”
for more information.
■
3E: PID Setpoint Selection 1
Setting Value
Function
Description
3E
PID Setpoint Selection 1
Set this function and
H1-xx = 3F [PID Setpoint Selection 2]
together. Sets the function to switch the PID setpoint to
b5-58 to b5-60
[PID Setpoint 2 to 4]
.
Refer to
“
b5-58 to b5-60: PID Setpoint 2 to 4
”
for more information.
■
3F: PID Setpoint Selection 2
Setting Value
Function
Description
3F
PID Setpoint Selection 2
Set this function and
H1-xx = 3E [PID Setpoint Selection 1]
at the same time. Sets the function to switch the PID setpoint to
b5-58
to b5-60 [PID Setpoint 2 to 4]
.
Refer to
b5-58 to b5-60: PID Setpoints 2 to 4 on page 195
for more information.
■
40: Forward RUN (2-Wire)
Setting Value
Function
Description
40
Forward RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 41 [Reverse Run Command (2-Wire Seq)]
at
the same time.
ON : Forward Run
OFF : Run Stop
Note:
•
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm
EF [FWD/REV Run Command
Input Error]
and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)]
.
Figure 2.68 2-Wire Sequence Wiring Example
■
41: Reverse RUN (2-Wire)
Setting Value
Function
Description
41
Reverse RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 40 [Forward Run Command (2-Wire Seq)]
at
the same time.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...