Table 74: WBM “ERPS” Page – “Ring Settings” Tab
ERPS Global Settings
Parameters
Default
Description
Global State
Disable
Select “Disable” in the selection box to disable the
ERPS function.
Enable
Select “Enable” in the selection box to enable the
ERPS function.
ERPS Ring Settings
Parameters
Default
Description
Ring ID
(1~255)
Enter the Ring ID in the input field.
State
Disable
Select “Disable” in the selection box to disable the
state of the ring.
Enable
Select “Enable” in the selection box to enable the
state of the ring.
Ring Name
Enter the name of the ring (max. 32 characters) in
the input field.
(e.g., Major-Ring ID255)
Revertive
Enable
Select “Enable” to enable revertive mode.
Disable
Select “Disable” in the selection box to disable the
revertive mode.
Instance
(0:Disable, 0~30)
Enter the instance for the ring in the input field.
Valid range: 0 … 30.
0 (“Disable”) means that the ERPS is running in
version 1. The control VLAN of the instance should
be the same as the control VLAN below it.
Ring Type
Major-ring
Select “Major-Ring” in the selection box if the
switch should operate in the Major-Ring.
Sub-ring
Select “Sub-Ring” in the selection box if the switch
should operate in the Sub-Ring.
Control VLAN
(1~4084)
1 … 4094
Enter the VLAN ID in the input field that should
serve as the domain for the ERPS control packets.
Version
v2
Select “v2” in the selection box if you want to use
ERPS Version v2.
v1
Select “v1” in the selection box if you want to use
ERPS Version v1.
Holdoff Timer (ms)
(0~10000)
0
… 10000
Enter the value for the “Hold-off Timer” for the ring
in the input field.
Valid range: 0 … 10000 ms.
WTR Timer (min)
(5~12)
5
… 12
Enter the value for the “WTR Timer” for the ring in
the input field.
MEL
(0~7)
0 …
7
Enter the value for the “Control MEL”
(
M
aintenance
E
ntity Group
L
evel) for the ring in the
input field.
The MEL specifies the priority.
0 = Lowest priority
7 = Highest priority