18
Installation
3.3
Connect motor and mains
cables for 0090 to 1500
VSD JNFX48-0090 to 0250 and JNFX69-0090
to 0175
To simplify the connection of thick motor and mains
cables to the VSD model JNFX48-0090 to 0250 and
JNFX69-0090 to 0175 the cable interface plate can be
removed.
Fig. 25 Connecting motor and mains cables
1. Remove the cable interface plate from the VSD
housing.
2. Put the cables through the glands.
3. Strip the cable according to Table 8.
4. Connect the stripped cables to the respective
mains/motor terminal.
5. Fix the clamps on appropriate place and tighten the
cable in the clamp with good electrical contact to
the cable screen.
6. Put the cable interface plate in place and secure
with the fixing screws.
VSD model 0300 to 1500
Fig. 26 Connecting motor and mains cables
VSD models 0300 to 1500 are supplied with Klockner
Moeller K3x240/4 power clamps.
For all type of wires to be connected the stripping
length should be 32 mm.
Cable interface
Clamps for screening
L1 L2 L3 PE
PE U V W