Main Features
47
Stopping an additional pump
This figure shows a possible sequence with all levels
and functions involved when an additional pump is
stopped by means of the pump control relays. The stop-
ping of the second pump is controlled by one of the
relay outputs. The relay in this example stops the pump
directly on line. Of course other start/stop equipment
like a soft starter could be controlled by the relay out-
put.
Fig. 56
Time sequence stopping an additional pump
(NG_50-PC-20_1)
Set view ref. [310]
Feedback Flow
time
Master pump
Max speed
Speed
Transition Speed Stop
Min speed
Lower band
Upper band
Stop delay [39A]
Settle time stop [39F]
Stop ramp depends
on start method
Stop command
Speed
2nd pump
time
time
[39G]
[343]
[341]