Functional Description
67
Communication information
11.2.2 Remote Signal Level/Edge
In this menu you select the way to control the inputs for
RunR, RunL, Stop and Reset that are operated via the
digital inputs on the terminal strip. The inputs are
default set for level-control, and will be active as long as
the input is made and kept high. When edge-control is
selected, the input will be activated by the low to high
transition of the input.
Communication information
11.2.3 Mains supply voltage [21B]
In this menu the nominal mains supply voltage con-
nected to the VSD can be selected. The setting will be
valid for all parameter sets. The default setting, Not
defined, is never selectable and is only visible until a
new value is selected.
Once the supply voltage is set, this selection will not be
affected by the Load Default command [243].
Brake chopper activation level is adjusted using the set-
ting of [21B].
Communication information
11.2.4 Motor Data [220]
In this menu you enter the motor data to adapt the VSD
to the connected motor. This will increase the control
accuracy as well as different read-outs and analogue
output signals.
Motor M1 is selected as default and motor data
entered will be valid for motor M1. If you have more
Modbus Instance no/DeviceNet no:
43019
Profibus slot/index
168/178
Fieldbus format
UInt
Modbus format
UInt
Default:
Level
Level
0
The inputs are activated or deactivated
by a continuous high or low signal. Is
commonly used if, for example, a PLC is
used to operate the VSD.
Edge
1
The inputs are activated by a transition;
for Run and Reset from “low” to “high”,
for Stop from “high” to “low”.
Modbus Instance no/DeviceNet no:
43020
Profibus slot/index
168/179
Fieldbus format
UInt
Modbus format
UInt
CAUTION: Level controlled inputs DO NOT
comply with the Machine Directive if the inputs
are directly used to start and stop the machine.
NOTE: Edge controlled inputs can comply with the
Machine Directive (see the Chapter 8. page 49) if the
inputs are directly used to start and stop the machine.
Stp
Level
A
!
WARNING: This menu must be set according
to the VSD product lable and the supply
voltage used. Wrong setting might damage
the VSD or brake resistor.
NOTE: The setting is affected by the Load from CP
command [245] and if loading parameter file via
EmoSoftCom.
Default:
Not defined
Not Defined 0
Inverter default value used. Only valid if
this parameter is never set.
220-240 V
1
Only valid for JNFX40/48
380-415 V
3
Only valid for JNFX40/48/50
440-480 V
4
Only valid for JNFX48/50/52
500-525 V
5
Only valid for JNFX50/52/69
550-600 V
6
Only valid for JNFX69
660-690 V
7
Only valid for JNFX69
Modbus Instance no/DeviceNet no:
43381
Profibus slot/index
170/30
Fieldbus format
UInt
Modbus format
UInt
Stp
Not defined
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...