Functional Description
11.5.4 Digital Outputs [540]
Submenu with all the settings for the digital outputs.
Sets the function for the digital output 1.
NOTE: The definitions described here are valid for the
active output condition.
Default:
Ready
Off
0
Output is not active and constantly
low.
On
1
Output is made constantly high, i.e.
for checking circuits and trouble
shooting.
Run
2
Running. The VSD output is active =
produces current for the motor.
Stop
3
The VSD output is not active.
0Hz
4
The output frequency=0±0.1Hz when
in Run condition.
Acc/Dec
5
The speed is increasing or decreasing
along the acc. ramp dec. ramp.
At Process
6
The output = Reference.
At Max spd
7
The frequency is limited by the Maxi-
mum Speed.
No Trip
8
No Trip condition active.
Trip
9
A Trip condition is active.
AutoRst Trip
10
Autoreset trip condition active.
Limit
11
A Limit condition is active.
Warning
12
A Warning condition is active.
Ready
13
The VSD is ready for operation and to
accept a start command. This means
that the VSD is powered up and
healthy.
T= T
lim
14
The torque is limited by the torque
limit function.
I>I
nom
15
The output current is higher than the
motor nominal current [224], reduced
according to Motor ventilation [228],
see Fig. 71.
Brake
16
The output is used to control a
mechanical brake.
Sgnl<Offset
17
One of the AnIn input signals is lower
than 75% of the threshold level.
Alarm
18
The max or min alarm level has been
reached.
Pre-Alarm
19
The max or min pre alarm level has
been reached.
Stp
Ready
A
Max Alarm
20
The max alarm level has been
reached.
Max PreAlarm 21
The max pre alarm level has been
reached.
Min Alarm
22
The min alarm level has been
reached.
Min PreAlarm 23
The min pre alarm Level has been
reached.
LY
24
Logic output Y.
!LY
25
Logic output Y inverted.
LZ
26
Logic output Z.
!LZ
27
Logic output Z inverted.
CA 1
28
Analogue comparator 1 output.
!A1
29
Analogue comp 1 inverted output.
CA 2
30
Analogue comparator 2 output.
!A2
31
Analogue comp 2 inverted output.
CD 1
32
Digital comparator 1 output.
!D1
33
Digital comp 1 inverted output.
CD 2
34
Digital comparator 2 output.
!D2
35
Digital comp 2 inverted output.
Operation
36
Run command is active or VSD run-
ning. The signal can be used to con-
trol the mains contactor if the VSD is
equipped with Standby supply option.
T1Q
37
Timer1 output
!T1Q
38
Timer1 inverted output
T2Q
39
Timer2 output
!T2Q
40
Timer2 inverted output
Sleeping
41
Sleeping function activated
Crane Deviat 42
Tripped on deviation
PumpSlave1
43
Activate pump slave 1
PumpSlave2
44
Activate pump slave 2
PumpSlave3
45
Activate pump slave 3
PumpSlave4
46
Activate pump slave 4
PumpSlave5
47
Activate pump slave 5
PumpSlave6
48
Activate pump slave 6
PumpMaster1 49
Activate pump master 1
PumpMaster2 50
Activate pump master 2
PumpMaster3 51
Activate pump master 3
PumpMaster4 52
Activate pump master 4
PumpMaster5 53
Activate pump master 5
PumpMaster6 54
Activate pump master 6
All Pumps
55
All pumps are running
Only Master
56
Only the master is running
Loc/Rem
57
Local/Rem function is active
Standby
58
Standby supply option is active
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...