
Functional Description
129
Communication information
Sets the function for the digital output 2.
Communication information
11.5.5 Relays [550]
Submenu with all the settings for the relay outputs. The
relay mode selection makes it possible to establish a
“fail safe” relay operation by using the normal closed
contact to function as the normal open contact.
Relay 1 [551]
Sets the function for the relay output 1. Same function
as digital output 1 [541] can be selected.
Communication information
PTC Trip
59
Trip when function is active
PT100 Trip
60
Trip when function is active
Overvolt
61
Overvoltage due to high main voltage
Overvolt G
62
Overvoltage due to generation mode
Overvolt D
63
Overvoltage due to deceleration
Acc
64
Acceleration along the acc. ramp
Dec
65
Deceleration along the dec. ramp
I
2
t
66
I
2
t limit protection active
V-Limit
67
Overvoltage limit function active
C-Limit
68
Overcurrent limit function active
Overtemp
69
Over temperature warning
Low voltage
70
Low voltage warning
DigIn 1
71
Digital input 1
DigIn 2
72
Digital input 2
DigIn 3
73
Digital input 3
DigIn 4
74
Digital input 4
DigIn 5
75
Digital input 5
DigIn 6
76
Digital input 6
DigIn 7
77
Digital input 7
DigIn 8
78
Digital input 8
ManRst Trip
79
Active trip that needs to be manually
reset
Com Error
80
Serial communication lost
External Fan
81
The VSD requires external cooling.
Internal fans are active.
LC Pump
82
Activate liquid cooling pump
LC HE Fan
83
Activate liquid cooling heat exchanger
fan
LC Level
84
Liquid cooling low level signal active
Run Right
85
Positive speed (>0.5%), i.e. forward/
clockwise direction.
Run Left
86
Negative speed (
≤
0.5%), i.e. reverse
counter clockwise direction.
Com Active
87
Fieldbus communication active.
Modbus Instance no/DeviceNet no: 43271
Profibus slot/index
169/175
Fieldbus format
UInt
Modbus format
UInt
NOTE: The definitions described here are valid for the
active output condition.
Default:
No trip
Selection:
Same as in menu
Modbus Instance no/DeviceNet no: 43272
Profibus slot/index
169/176
Fieldbus format
UInt
Modbus format
UInt
NOTE: Additional relays will become available when I/O
option boards are connected. Maximum 3 boards with 3
relays each.
Default:
Trip
Selection:
Same as in menu
]
Modbus Instance no/DeviceNet no: 43273
Profibus slot/index
169/177
Fieldbus format
UInt
Modbus format
UInt
Stp
No Trip
A
Stp
Trip
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...