100
Functional Description
Fig. 86 MotPot function
Preset Ref 1 [362] to Preset Ref 7
[368]
Preset speeds have priority over the analogue inputs.
Preset speeds are activated by the digital inputs. The
digital inputs must be set to the function Pres. Ref 1,
Pres. Ref 2 or Pres. Ref 4.
Depending on the number of digital inputs used, up to
7 preset speeds can be activated per parameter set.
Using all the parameter sets, up to 28 preset speeds
are possible
.
Communication information
The same settings are valid for the menus:
[363] Preset Ref 2, with default 250 rpm
[364] Preset Ref 3, with default 500 rpm
[365] Preset Ref 4, with default 750 rpm
[366] Preset Ref 5, with default 1000 rpm
[367] Preset Ref 6, with default 1250 rpm
[368] Preset Ref 7, with default 1500 rpm
The selection of the presets is as in Table 24.
1)
= selected if only one preset reference is active
1 = active input
0 = non active input
Keyboard reference mode [369]
This parameter sets how the reference value [310] is
edited.
Communication information
Default:
Speed, 0 rpm
Dependent on: Process Source [321] and Process Unit [322]
Speed mode
0 - max speed [343]
Torque mode
0 - max torque [351]
Other modes
Min according to menu [324] - max according
to menu [325]
Modbus Instance no/DeviceNet no:
43132–43138
Profibus slot/index
169/36–169/42
Fieldbus format
Long
Modbus format
EInt
t
t
n
t
Motpot
UP
Motpot
DOWN
Stp
0rpm
A
Table 24
Preset
Ctrl3
Preset
Ctrl2
Preset
Ctrl1
Output Speed
0
0
0
Analogue reference
0
0
1
1)
Preset Ref 1
0
1
1)
0
Preset Ref 2
0
1
1
Preset Ref 3
1
1)
0
0
Preset Ref 4
1
0
1
Preset Ref 5
1
1
0
Preset Ref 6
1
1
1
Preset Ref 7
NOTE: If only Preset Ctrl3 is active, then the Preset Ref 4
can be selected. If Presets Ctrl2 and 3 are active, then
the Preset Ref 2, 4 and 6 can be selected.
Default:
Normal
Normal
0
The reference value is edited as a normal
parameter (the new reference value is
activated when Enter is pressed after the
value has been changed). The Acc Time
[331] and Dec Time [332] are used.
MotPot
1
The reference value is edited using the
motor potentiometer function (the new
reference value is activated directly when
the key + or - is pressed). The Acc MotPot
[333] and Dec MotPot [334] are used.
Modbus Instance no/DeviceNet no:
43139
Profibus slot/index
169/43
Fieldbus format
UInt
Modbus format
UInt
NOTE: When Key Ref Mode is set to MotPot, the
reference value ramp times are according to the Acc
MotPot [333] and Dec MotPot [334] settings. Actual
speed ramp will be limited according to Acc Time [331]
and Dec Time [332].
Stp
Normal
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...