Functional Description
139
11.6.4 Timer1 [640]
The Timer functions can be used as a delay timer or as
an interval with separate On and Off times (alternate
mode). In delay mode, the output signal T1Q becomes
high if the set delay time is expired. See Fig. 111.
Fig. 111
In alternate mode, the output signal T1Q will switch
automatically from high to low etc. according to the set
interval times. See Fig. 112.
The output signal can be programmed to the digital or
relay outputs used in logic functions [620] and [630],
or as a virtual connection source [560].
Fig. 112
Timer 1 Trig [641]
Communication information
Communication information
Timer 1 Delay [643]
This menu is only visible when timer mode is set to
delay.
This menu can only be edited as in alternative 2, see
section 9.5, page 54.
Timer 1 delay sets the time that will be used by the first
timer after it is activated. Timer 1 can be activated by a
high signal on a DigIn that is set to Timer 1 or via a vir-
tual destination [560].
Communication information
NOTE: The actual timers are common for all parameter
sets. If the actual set is changed, the timer functionality
[641] to [645] will change according set settings but the
timer value will stay unchanged. So initialization of the
timer might differ for a set change compared to normal
triggering of a timer.
Default:
Off
Selection: Same selections as Digital Output 1 menu [541].
Modbus Instance no/DeviceNet no: 43431
Profibus slot/index
170/80
Fieldbus format
UInt
Modbus format
UInt
Timer1 Trig
T1Q
Timer1 delay
T1
T2
T1
T2
Timer1 Trig
T1Q
Stp
Off
A
Default:
Off
Off
0
Delay
1
Alternate
2
Modbus Instance no/DeviceNet no: 43432
Profibus slot/index
170/81
Fieldbus format
UInt
Modbus format
UInt
Default:
0:00:00 (hr:min:sec)
Range:
0:00:00–9:59:59
Modbus Instance no/DeviceNet no:
43433 hours
43434 minutes
43435 seconds
Profibus slot/index
170/82, 170/83,
170/84
Fieldbus format
UInt
Modbus format
UInt
Stp
Off
A
Stp
0:00:00
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...