Functional Description
The default set levels for the (pre)alarms are:
These default set levels can be manually changed in
menus [416] to [419]. After execution the message
“Autoset OK!” is displayed for 1s and the selection
reverts to “No”.
Normal Load [41B]
Set the level of the normal load. The alarm or pre alarm
will be activated when the load is above/under normal
load ± margin.
Communication information
Load Curve [41C]
The load curve function can be used with any smooth
load curve. The curve can be populated with a test-run
or the values can be entered or changed manually.
Load Curve 1-9 [41C1]-[41C9]
The measured load curve is based on 9 stored sam-
ples. The curve starts at minimum speed and ends at
maximum speed, the range in between is divided into 8
equal steps. The measured values of each sample are
displayed in [41C1] to [41C9] and can be adapted man-
ually. The value of the 1st sampled value on the load
curve is displayed.
Communication information
Fig. 99
Overload
Max Alarm
Max Pre Alarm menu [4171] + [41B]
Underload
Min Pre Alarm menu [41B] - [4181]
Min Alarm
Default:
100%
Range:
0-400% of max torque
NOTE: 100% Torque means: I
NOM
= I
MOT
. The maximum
depends on the motor current and VSD max current
settings, but the absolute maximum adjustment is
400%.
Modbus Instance no/DeviceNet no: 43335
Profibus slot/index
169/239
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
100%
Range:
0–400% of max torque
Stp
100%
A
Stp
0rpm 100%
A
Modbus Instance no/DeviceNet no:
43336%, 43337 rpm,
43338%, 43339 rpm,
43340%, 43341 rpm,
43342%, 43343 rpm,
43344%, 43345 rpm,
43346%, 43347 rpm,
43348%, 43349 rpm,
43350%, 43351 rpm,
43352%, 43353 rpm
Profibus slot/index
169/240, 169/242,
169/244, 169/246,
169/248, 169/250,
169/252, 169/254,
170/1
Fieldbus format
Long
Modbus format
EInt
NOTE: The speed values depend on the Min- and Max
Speed values. they are read only and cannot be
changed.
0
0.2
0.4
0.6
0.8
1
0
0.5
1
Min Speed
Speed
Max Speed
Min-Max alarm tolerance band graph
Measured load samples
Min-max tolerance band
Max alarm limit
Min alarm limit
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...