72
Functional Description
Motor I
2
Sets the current limit for the motor I
2
t protection.
Communication information
Motor I
2
t Time [233]
Sets the time of the I
2
t function. After this time the limit
for the
I
2
t is reached if operating with 120% of the I
2
t
current value. Valid when start from 0 rpm.
Communication information
Fig. 72 I
2
t function
Fig. 72 shows how the function integrates the square of
the motor current according to the Mot I
2
t Curr [232]
and the Mot I
2
Profibus slot/index
168/220
Fieldbus format
UInt
Modbus format
UInt
NOTE: When Mot I2t Type=Limit, the VSD can control the
speed < MinSpeed to reduce the motor current.
Default:
100% of I
MOT
Range:
0–150% of I
MOT
Modbus Instance no/DeviceNet no:
43062
Profibus slot/index
168/221
Fieldbus format
Long, 1=1%
Modbus format
EInt
NOTE: When the selection Limit is set in menu [231], the
value must be above the no-load current of the motor.
2
t Curr
Stp
100%
A
NOTE: Not the time constant of the motor.
Default:
60 s
Range:
60–1200 s
Modbus Instance no/DeviceNet no:
43063
Profibus slot/index
168/222
Fieldbus format
Long, 1=1 s
Modbus format
EInt
2
t Time
Stp
M1:
60
s
A
10
100
1000
10000
100000
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2
t [s]
i / I2t-current
60 s (120%)
120 s (120%)
240 s (120%)
480 s (120%)
1000 s (120%)
Actual output current/ I
2
t-current
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...