Functional Description
111
Communication information
Ramp Alarm [413]
This function inhibits the (pre) alarm signals during
acceleration/deceleration of the motor to avoid
false
alarms.
Communication information
Alarm Start Delay [414]
This parameter is used if, for example, you want to over-
ride an alarm during the start-up procedure.
Sets the delay time after a run command, after which
the alarm may be given.
• If Ramp Alarm=On. The start delay begins after a
RUN command.
•
If Ramp Alarm=Off. The start delay begins after the
acceleration ramp.
Communication information
Load Type [415]
In this menu you select monitor type according to the
load characteristic of your application. By selecting the
required monitor type, the overload and underload
alarm function can be optimized according to the load
characteristic.
When the application has a constant load over the
whole speed range, i.e. extruder or screw compressor,
the load type can be set to basic. This type uses a sin-
gle value as a reference for the nominal load. This value
is used for the complete speed range of the VSD. The
value can be set or automatically measured. See Auto-
set Alarm [41A] and Normal Load [41B] about setting
the nominal load reference.
The load curve mode uses an interpolated curve with 9
load values at 8 equal speed intervals. This curve is
populated by a test run with a real load. This can be
used with any smooth load curve including constant
load.
Fig. 98
Communication information
Modbus Instance no/DeviceNet no: 43322
Profibus slot/index
169/226
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
(Pre) alarms are inhibited during accelera-
tion/deceleration.
On
1
(Pre) alarms active during acceleration/
deceleration.
Modbus Instance no/DeviceNet no: 43323
Profibus slot/index
169/227
Fieldbus format
UInt
Modbus format
UInt
Default:
2 s
Range:
0-3600 s
Modbus Instance no/DeviceNet no: 43324
Profibus slot/index
169/228
Fieldbus format
Long, 1=1 s
Modbus format
EInt
Stp
Off
A
Stp
2s
A
Default:
Basic
Basic
0
Uses a fixed maximum and minimum load
level over the full speed range. Can be used
in situations where the torque is independ-
ent of the speed.
Load
Curve
1
Uses the measured actual load characteris-
tic of the process over the speed range.
Modbus Instance no/DeviceNet no: 43325
Profibus slot/index
169/229
Fieldbus format
UInt
Modbus format
UInt
Basic
Load curve
Load
Speed
Max Alarm
Min Alarm
Stp
Basic
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...