Functional Description
Press Enter to set up the parameters for fieldbus com-
munication.
Enter the unit address of the VSD.
Process Data Mode [2632]
Enter the mode of process data (cyclic data). For fur-
ther information, see the Fieldbus option manual.
Read/Write [2633]
Select read/write to control the inverter over a fieldbus
network. For further information, see the Fieldbus
option manual.
Additional Process Values [2634]
Define the number of additional process values sent in
cyclic messages.
Communication Fault [264]
Main menu for communication fault/warning settings.
For further details please see the Fieldbus option man-
ual.
Communication Fault Mode [2641]]
Selects action if a communication fault is detected.
Communication information
Default:
1
Selection:
1–247
Default:
62
Range:
Profibus 0–126, DeviceNet 0–63
Node address valid for Profibus and DeviceNet
Default:
Basic
None
0
Control/status information is not used.
Basic
4
4 byte process data control/status informa-
tion is used.
Extended
8
4 byte process data (same as Basic set-
ting) + additional proprietary protocol for
advanced users is used.
Default:
RW
RW
0
Read
1
Valid for process data. Select R (read only) for logging proc-
ess without writing process data. Select RW in normal cases
to control inverter.
Stp
1
A
Stp
A
Stp
62
A
Stp
Basic
A
Stp
RW
A
Default:
0
Range:
0-8
Default:
Off
Off
0
No communication supervision.
Trip
1
RS232/485 selected:
The VSD will trip if there is no communica-
tion for time set in parameter [2642].
Fieldbus selected:
The VSD will trip if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
Warning
2
RS232/485 selected:
The VSD will give a warning if there is no
communication for time set in parameter
[2642].
Fieldbus selected:
The VSD will give a warning if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
NOTE: Menu [214] and/or [215] must be set to COM to
activate the communication fault function.
Modbus Instance no/DeviceNet no:
43037
Profibus slot/index
168/196
Fieldbus format
UInt
Modbus format
UInt
Stp
0
A
Stp
Off
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...