Operation via the Control Panel
51
9.
Operation via the Control Panel
This chapter describes how to use the control panel.
The VSD can be delivered with a control panel or a
blank panel.
9.1
General
The control panel displays the status of the VSD and is
used to set all the parameters. It is also possible to con-
trol the motor directly from the control panel. The con-
trol panel can be built-in or located externally via serial
communication. The VSD can be ordered without the
control panel. Instead of the control panel there will be
a blank panel.
9.2
The control panel
Fig. 57 Control panel
9.2.1 The display
The display is back lit and consists of 2 rows, each with
space for 16 characters. The display is divided into six
areas.
The different areas in the display are described below:
Fig. 58 The display
Area A:
Shows the actual menu number (3 or 4
digits).
Area B
Shows if the menu is in the toggle loop or
the VSD is set for Local operation.
Area C:
Shows the heading of the active menu.
Area D:
Shows the status of the VSD (3 digits).
The following status indications are possi ble:
Acc : Acceleration
Dec : Deceleration
I
2
t :
Active
I
2
t protection
Run : Motor runs
Trp : Tripped
Stp : Motor is stopped
VL
: Operating at Voltage limit
SL
: Operating at Speed limit
CL
: Operating at Current limit
TL
: Operating at Torque limit
OT
: Operating at Temperature Limit
LV
: Operating at Low Voltage
Sby : Operating from Standby power supply
SST : Operating Safe Stop, is blinking when
activated
LCL : Operating with low cooling liquid level
Area E:
Shows active parameter set and if it is a
motor parameter.
Area F:
Shows the setting or selection in the active
menu.This area is empty at the 1st level and
2nd level menu. This area also shows warn-
ings and alarm messages.
Fig. 59 Example 1st level menu
Fig. 60 Example 2nd level menu
Fig. 61 Example 3d level menu
Fig. 62 Example 4th level menu
NOTE: The VSD can run without the control panel being
connected. However the settings must be such that all
control signals are set for external use.
LC Display
LEDs
Control Keys
Toggle Key
Function Keys
Motor Volt
Stp
M1:
400V
T
A
A
C
D
F
B
E
A
A
M1:
400V
A
0.1s
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...