120
Functional Description
Communication information
AnIn1 Function Max [5136]
With AnIn1 Function Max the physical maximum value
is scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511]. See
Table 25.
Communication information
AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5136]
.
Communication information
Example:
Process sensor is a sensor with the following specifica-
tion:
Range:
0–3 bar
Output:
2–10 mA
Analogue input should be set up according to:
[512] AnIn1 Setup = User mA
[5131] AnIn1 Min = 2 mA
[5132] AnIn1 Max = 10 mA
[5134] AnIn1 Function Min = User-defined
[5135] AnIn1 VaMin = 0.000 bar
[5136] AnIn 1 Function Max = User-defined
[5137] AnIn1 VaMax = 3.000 bar
Communication information
AnIn1 Filter [5139]
If the input signal is unstable (e.g. fluctuation reference
value), the filter can be used to stabilize the signal. A
change of the input signal will reach 63% on AnIn1
within the set AnIn1 Filter time. After 5 times the set
time, AnIn1 will have reached 100% of the input
change. See Fig. 105.
Modbus Instance no/DeviceNet no: 43541
Profibus slot/index
170/190
Fieldbus format
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
Modbus format
EInt
Default:
Max
Min
0
Min value
Max
1
Max value
User-defined 2
Define user value in menu [5137]
Modbus Instance no/
DeviceNet no:
43207
Profibus slot/index
169/111
Fieldbus format
Long,
Speed/Torque 1=1 rpm or %.
Other 1= 0.001
Modbus format
EInt
Default:
0.000
Range:
-10000.000 – 10000.000
Modbus Instance no/DeviceNet no: 43551
Profibus slot/index
170/200
Fieldbus format
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
Modbus format
EInt
Stp
Max
A
Stp
0.000
A
NOTE: With AnIn Min, AnIn Max, AnIn Function Min and
AnIn Function Max settings, loss of feedback signals
(e.g. voltage drop due to long sensor wiring) can be
compensated to ensure an accurate process control.
Default:
Add+
Add+
0
Analogue signal is added to selected func-
tion in menu
Sub-
1
Analogue signal is subtracted from
selected function in menu
].
Modbus Instance no/DeviceNet no: 43208
Profibus slot/index
169/112
Fieldbus format
UInt
Modbus format
UInt
Default:
0.1 s
Range:
0.001 – 10.0 s
Stp
Add+
A
Stp
0.1s
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...