110
Functional Description
Communication information
Reset Run Times 1-6 [39H1] to [39M1]
Communication information
Pump Status [39N]
11.4 Load Monitor and Process
Protection [400]
11.4.1 Load Monitor [
]
The monitor functions enable the VSD to be used as a
load monitor. Load monitors are used to protect
machines and processes against mechanical overload
and underload, e.g. a conveyer belt or screw conveyer
jamming, belt failure on a fan and a pump dry running.
See explanation in section 7.5, page 38.
Selects the types of alarms that are active.
Communication information
Alarm Trip [412]
Selects which alarm must cause a trip to the VSD.
Unit:
h:m (hours:minutes)
Range:
0h:0m–65535h:59m.
Modbus Instance no/
DeviceNet no:
31051 hours, 31052 minutes,
31054 hours, 31055 minutes,
31057 hours, 31058 minutes,
31060 hours, 31061 minutes,
31063 hours, 31064 minutes,
31066 hours, 31067 minutes
Profibus slot/index
121/195, 121/198, 121/201,
121/204, 121/207, 121/210
Fieldbus format
UInt
Modbus format
UInt
Default:
No
No
0
Yes
1
Modbus Instance no/DeviceNet no:
38–43, pump 1 -6
Profibus slot/index
0/37–0/42
Fieldbus format
UInt
Modbus format
UInt
Indication
Description
C
Control, master pump, only when alternating
master is used
D
Direct control
O
Pump is off
E
Pump error
A
Stp
h:mm
A
Stp
No
Stp
OCD
A
Default:
Off
Off
0
No alarm functions active.
Min
1
Min Alarm active. The alarm output func-
tions as an underload alarm.
Max
2
Max Alarm active. The alarm output func-
tions as an overload alarm.
Max+Min 3
Both Max and Min alarm are active. The
alarm outputs function as overload and
underload alarms.
Modbus Instance no/DeviceNet no: 43321
Profibus slot/index
169/225
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Selection:
Same as in menu [411]
Stp
Off
A
Stp
Off
A
Summary of Contents for F33 Series
Page 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Page 3: ......
Page 33: ...30 Getting Started...
Page 51: ...48 Main Features...
Page 53: ...50 EMC and Machine Directive...
Page 59: ...56 Operation via the Control Panel...
Page 65: ...62 Serial communication...
Page 159: ...156 Troubleshooting Diagnoses and Maintenance...
Page 165: ...162 Options...
Page 179: ...176 Technical Data...
Page 187: ...184 Menu List...